Holidays period
12
Date of first day of
holiday
13
Date of last day of
en
holiday
14
Heating curve, flow
setpoint at 15 °C
outside temperature
15
Heating curve, flow
setpoint at –5 °C
outside temperature
38
Time of day
39
Weekday
40
Date
41
Year
50
Faults
Building Technologies
-
(1...8)
.........................
--.--
(01.01 ... 31.12)
.........................
--.--
(01.01 ... 31.12)
.........................
30 °C
(20...70)
...................
60 °C
(20...120)
...................
00:00...23:59
Display function
(01.01 ... 31.12)
.........................
(1995...2094)
.........................
Display function
Display example for intercon-
nected plants:
10 = error code
2 = segment number (LPB)
03 = unit number(LPB)
74 319 0617 0 a
Day.Month
Day.Month
These operating lines are only
°C
active if digital adjustment of the
heating curve has been
selected (refer to entry made on
°C
operating line 73)
Hours:Minutes
1 = Monday
2 = Tuesday
7 = Sunday
Day.Month (e.g. 02.12 for
2. Dec.)
10 = fault outside sensor
30 = fault flow or boiler tem-
perature sensor
40 = fault return temperature
sensor (primary circuit)
42 = fault return temperature
sensor (secondary circuit)
60 = fault room temperature
sensor
61 = fault room unit
62 = wrong room unit con-
nected
81 = short-circuit on data bus
82 = same bus address used
several times
17.04.2008
30/180