Specifications - Danfoss VLT Micro Drive FC 51 Guide Rapide

Masquer les pouces Voir aussi pour VLT Micro Drive FC 51:
Table des Matières

Publicité

Quick Guide

1.7 Specifications

1.7.1 Mains Supply 1x200–240 V AC
Normal overload 150% for 1 minute
Frequency converter
Typical shaft output [kW]
Typical shaft output [hp]
Enclosure protection rating IP20
Output current
Continuous (3x200–240 V AC) [A]
Intermittent (3x200–240 V AC) [A]
Maximum cable size:
2
(Mains, motor) [mm
/AWG]
Maximum input current
Continuous (1x200–240 V) [A]
Intermittent (1x200–240 V) [A]
Maximum mains fuses [A]
Environment
Estimated power loss [W],
1)
Best case/typical
Weight enclosure IP20 [kg]
Efficiency [%],
2)
Best case/typical
Table 1.7 Mains Supply 1x200–240 V AC
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to
drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
2) Efficiency measured at nominal current. For energy efficiency class, see chapter 1.8.1 Surroundings. For part load losses, see drives.danfoss.com/
knowledge-center/energy-efficiency-directive/#/.
MG02BC4P
Quick Guide•Kurzanleitung•Guide rapide•Guía rápida•Guia Rápido•Краткое
руководство
Danfoss A/S © 10/2017 All rights reserved.
PK18
PK37
PK75
0.18
0.37
0.75
0.25
0.5
1
M1
M1
M1
1.2
2.2
4.2
1.8
3.3
6.3
4/10
3.3
6.1
11.6
4.5
8.3
15.6
See chapter 1.3.3 Fuses
12.5/
20.0/
36.5/
15.5
25.0
44.0
1.1
1.1
1.1
95.6/
96.5/
96.6/
94.5
95.6
96.0
1
P1K5
P2K2
1.5
2.2
2
3
M2
M3
6.8
9.6
10.2
14.4
18.7
26.4
26.4
37.0
61.0/
81.0/
67.0
85.1
1.6
3.0
97.0/
96.9/
96.7
97.1
23
1