Service tasks
"Service completed" displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.4
Calibrating the pressure transducer
I
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
Every four weeks
If the AirCon Service Center has been subjected to heavy shaking
Every time the vacuum pump oil is changed
If the display shows implausible pressure readings
1. In the basic menu, use the cursor keys or to select "Other
selections":
2. Depressurise the unit (as described in chapter "Changing the dryer
filter" on page 97).
3. Press ENTER to confirm.
4. Use the cursor keys or to select "Service":
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
100
Service completed:
Number
STOP-EXIT
Short selection
Free selection
Other selections
ENTER-OK
Service.
ENTER-OK STOP-EXIT
ASC 1100G
08/03/20
4
EN