ASC 1100G
9.6
Meter readings
I
NOTE
The unit saves various meter readings. To access the total values –
consecutively, since the unit was produced – enter the menu "Other
selections" – "Service" and enter the code "7783". Use the cursor
keys or to select a particular entry.
These meter readings cannot be reset. To access the meter readings
which can be reset, enter the code "7782" under "Service". Also see
chapter "Changing the vacuum pump oil" on page 102 or chapter
"Changing the dryer filter" on page 97.
"R134a from system" indicates how many grams of refrigerant have
been extracted from air conditioning systems using the menu item "Short
selection" or "Free selection" since the last reset (see date).
"R134a from tank" indicates how many grams of refrigerant were added
to the unit using the menu item "Int. vessel filling" since the last reset
(see date).
"R134a to system" indicates how many grams of refrigerant have been
filled into air conditioning systems using the menu item "Short selec-
tion" or "Free selection" since the last reset (see date).
"Vacuum time" indicates how long the vacuum pump has operated
since the last reset (see date).
EN
R134a from system
g.
STOP-EXIT
R134a from tank
g.
STOP-EXIT
R134a to system
g.
STOP-EXIT
Vacuum time
min.
STOP-EXIT
Service tasks
07/03/20
1455
07/03/20
3395
07/03/20
1200
07/03/20
79