Calibrating The Pressure Transducer - Waeco AirConServiceCenter ASC5100G Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 171
ASC 5100G
"Service completed" displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.4

Calibrating the pressure transducer

I
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
 Every four weeks
 If the AirCon Service Center has been subjected to heavy shaking
 Every time the vacuum pump oil is changed
 If the display shows implausible pressure readings
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Depressurise the unit (as described in chapter "Changing the dryer
filter" on page 94).
3. Press ENTER to confirm.
4. Use the cursor keys  or  to select "Service":
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
EN
Service completed:
Number
STOP-EXIT
Short selection
Free selection
Other selections
ENTER-OK
Service.
ENTER-OK STOP-EXIT
Service tasks
08/03/17
4
97

Publicité

Table des Matières
loading

Table des Matières