Operation
BYPASS MODE:
BYPASS is an operating mode where the UPS is passing unprocessed
input power directly through to the output. BYPASS MODE can
engage on an automatic basis (AUTO-BYPASS) as an emergency
UPS operating mode that maintains output to connected equipment
in case of UPS overload or internal component failure that would
otherwise cause connected equipment to lose power. AUTO-BYPASS
MODE operation resulting from sudden UPS overload as the UPS is
running in ON LINE MODE will automatically reset, once the output
load is reduced. BYPASS MODE resulting from internal UPS failure
may not automatically reset, and if the message persists, users
should contact Tripp Lite for troubleshooting or repair options.
Regardless of the cause, the UPS will not provide battery backup
anytime the UPS is running in BYPASS MODE.
BYPASS MODE SAMPLE LCD SCREEN
LCD ELEMENTS CONFIRMING BYPASS MODE OPERATION
> INPUT ICON: ON SOLID (input power is present, bypass is available)
> SINE WAVE PLUS DOT ICON: ON (CONFIRMS BYPASS MODE)
BYPASS MODE LCD VIEWING OPTIONS:
When the UPS enters BYPASS MODE, the LCD screen will continue
reporting the last viewed informational screen (INPUT VOLTAGE
shown). To display additional information screens, tap the SETUP
button repeatedly. The 10 available information screens are (1)
INPUT VOLTAGE, (2) INPUT FREQUENCY, (3) OUTPUT VOLTAGE, (4)
OUTPUT FREQUENCY, (5) LOAD PERCENTAGE, (6) LOAD KVA, (7)
LOAD KW, (8) BATTERY CHARGE PERCENT, (9) BATTERY VOLTAGE,
(10) ESTIMATED RUNTIME.
13-03-138 93-3168-EN.indd 17
STANDBY MODE:
When first connected to a live power source, the UPS will
automatically energize in Standby mode and report OFF on the LCD
screen. The charger will activate as necessary, but there is no UPS
output or battery backup support available in this mode. To turn the
UPS on for normal operation, press and hold the ON button until a
beep is heard; the UPS will energize after a series of diagnostic tests
are completed. To turn the UPS completely off from standby mode,
just unplug the UPS from its power source; the UPS will turn OFF and
the fan and LCD screen will turn off after approximately 30 seconds.
STANDBY MODE SAMPLE LCD SCREEN
LCD ELEMENTS CONFIRMING STANDBY MODE OPERATION
> 3 CHARACTER DISPLAY: OFF (CONFIRMS OUTPUT POWER IS OFF)
STANDBY MODE LCD VIEWING OPTIONS:
When the UPS enters STANDBY MODE, the LCD screen will report
OUTPUT OFF to confirm that output power is not available. To display
additional information screens, tap the SETUP button repeatedly. The
10 available information screens are (1) INPUT VOLTAGE, (2) INPUT
FREQUENCY, (3) OUTPUT VOLTAGE, (4) OUTPUT FREQUENCY, (5)
LOAD PERCENTAGE, (6) LOAD KVA, (7) LOAD KW, (8) BATTERY
CHARGE PERCENT, (9) BATTERY VOLTAGE, (10) ESTIMATED RUNTIME.
17