LoRaWAN 863-870 Pulse - Guide utilisateur / User guide version V2.0.0
3.3.1
Function register
The list of registers below allows you to change the behavior of the product application.
Regis-
Size
Description
ter
(bytes)
Transmission period of
S300
N/A
the Keep Alive frame
S301
2
Transmission period of
data sensors
S303
1
Confirmed mode acti-
vation
S304
2
PIN code
S306
1
Global operation
S320
1
Channels configuration
(A and B)
Coding
Details
Ignored value, the period is set to 24 hours (not
---
configurable) in OPERATION mode and 5 minutes
in TEST mode
Decimal
Default value: 1440
Min/max : 1 to 1440
Unit:
x 1min if S306=1
x 20s if S306=2
Decimal
Default value : 0 (deactivated)
Values : 0 (deactivated) to 1 (activated)
Decimal
Default value : 0 (disabled)
Min/max : 0 to 9999
PIN code used with ATPIN command.
Value 0 disables the PIN code.
IMPORTANT: The product does not have a mech-
anism
to unlock the PIN code if it is activated and the
code is forgotten.
Decimal
Default value: 0
Allows the product to be switched into one of the
following modes:
• 0: PARK mode
• 1: Production mode
• 2: TEST mode
• 3: REPLI mode
Hexadec-
Default value: 0x11
imal
For channel A :
•
Bit 0 : channel A activation
• Value 0: channel deactivated
• Value 1: channel activated
•
Bit 1 : meter type channel A (pull-up activa-
tion)
• Value 0: meter other than Gas (pull-up de-
activated)
• Value 1: Gas meter (pull-up activated)
•
Bit 2 : Reserved
•
Bit 3 : tamper input channel A
• Value 0: deactivated
• Value 1: activated
For channel B :
•
Bit 0 : channel B activation
• Value 0: channel deactivated
• Value 1: channel activated
•
Bit 1 : meter type channel B (pull-up activa-
tion)
• Value 0: meter other than Gas (pull-up de-
activated)
• Value 1: Gas meter (pull-up activated)
•
Bit 2 : Reserved
•
Bit 3 : tamper input channel B
• Value 0: deactivated
• Value 1: activated