LoRaWAN 863-870 Pulse - Guide utilisateur / User guide version V2.0.0
2.1.4
REPLI mode
The product enters this very low consumption mode following the detection of a level of battery that is
too low. In this mode the product wakes up every 5 seconds to make the red LED flash twice.
The replacement of the battery (if the product is a replaceable battery version) followed by the applica-
tion of the magnet takes the product out of this mode to return it to the operating mode.
2.2. Application operation
FR
2.2.1
Periodic transmission
The product allows the measurement and the periodic transmission of the values of the sensors accord-
ing to the following diagram:
EN
The settings associated with this mode of operation are:
•
Transmission period (register 301)
•
Enabling and Configuring inputs (register 320)
•
Anti-bounce timer period (registers S322)
A complete list of the registers can be found in paragraph 3.4.
Eg:
Register
Value encoding
S301
Decimal
S320
Hexadecimal
S322
Hexadecimal
No
Period
reached?
Yes
Send frame 0x46
Value
6
0x39
0x57
Product in
standby
Detected
and validat-
ed pulse
?
Yes
Counting of the
impulse
Result
Periodic mode with a period of 6x10min = 60
minutes
Channel A :
•
Activated
•
Meter other than gas
•
Tamper input activated
Channel B :
•
Activated
•
Gas meter
•
Tamper input disabled
Anti-rebound :
•
Channel A = 500ms
•
Channel B = 100ms