Error Description - Helios ALB EC 30/20 EH Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
Error
4 - Supply air fan error
6 - Supply air filter blo-
cked
8 - Failure of pre-hea-
ter 1
9 - Heater battery 1 error
12 - CO2 sensor error
16 - Supply air -
Damage to external
temperature sensor
(T-EXT1)
17 - Supply air - Defective
temperature sensor after
heater battery (T-EXT2)
18 - Supply air -
Defective temperature in
supply air duct (T-EXT3)
24 - Error concerning
water return temperature
sensor
(T_WATER_OUT)
25 - Error concerning
room temperature sensor
(T_Room)
27 - Error concerning
supply air filter pressure
sensor
28 - Error concerning
supply air fan pressure
sensor
32 - Error concerning air
quality sensor
34 - Error concerning ex-
ternal temperature sensor
from BMS
50 - Supply air filter blo-
cked > 80 %
70 - Water heater battery
frost protection
71 - Water heater - Wait
for the water temperature
72 - Water heater - Wait
for the supply air tempe-
rature
74 - Flow rate reduction,
minimum temperature in
duct not reached
Fresh Air Boxes – ALB EC
The generally applicable safety at work and accident prevention regulations must be observed!
– Electrical work must only be carried out by an authorised electrician.
– Use appropriate lifting equipment and fastening devices to dismantle the fan, Observe transport sketch!
– Dispose of the fan components according to the valid rules and laws.
7 .5

Error description

Unit behaviour
Unit does not function. Fan overheating or damage to the ther-
mal contacts of the supply air fan.
Unit ventilates.
Filter blocked.
Unit ventilates.
Pre-heater overheating.
Unit ventilates.
Heater battery overheating or damage
to temperature sensor.
Unit ventilates.
Malfunction of air quality sensor.
Temperature sensor error.
Unit does not fun-
ction.
Unit does not function. Temperature sensor error.
Temperature sensor error.
Unit does not fun-
ction.
Unit does not function. Temperature sensor error.
Unit ventilates.
Temperature sensor error.
Unit ventilates.
Pressure sensor error.
Unit does not function. Pressure sensor error.
Unit ventilates.
Malfunction of air quality sensor.
Unit ventilates.
Sensor error at BMS or incorrect data
Unit ventilates.
Filter blocked.
Unit ventilates.
Water heater battery frost protection is
active.
Unit ventilates.
Water temperature assessment active.
Unit ventilates.
Supply air temperature assessment.
Unit functions in limited
The unit attempts to reach the mini-
mode.
mum temperature.
Problem
Determine cause of motor overheating (e.g. faulty bearing, mechanical prob-
lem, short circuit, ...). The motor must be replaced, if necessary.
Check condition of filter and replace filter, if necessary.
Check whether the air can flow freely through the unit and the electric
pre-heater has sufficiently cooled down. Check the activation of the safety
temperature limiter.
Check whether the air can flow through the unit freely.
Check whether the CO2 sensor is connected correctly. Check function of
the CO2 sensor, if necessary (output signal value).
Check whether the sensor is correctly connected to the electronics. Carry
out a function test with the sensor by means of resistance measurement, if
necessary (the resistance value at +20 °C is around 10 kΩ).
Check whether the sensor is correctly connected to the electronics. Carry
out a function test with the sensor by means of resistance measurement, if
necessary (the resistance value at +20 °C is around 10 kΩ).
Check whether the sensor is correctly connected to the electronics. Carry
out a function test with the sensor by means of resistance measurement,
if necessary (the resistance value at +20 °C is around 10 kΩ).
Check whether the sensor is correctly connected to the electronics. Carry
out a function test with the sensor by means of resistance measurement, if
necessary (the resistance value at +20 °C is around 10 kΩ).
Check whether the sensor is correctly connected to the electronics. Carry
out a function test with the sensor by means of resistance measurement, if
necessary (the resistance value at +20 °C is around 10 kΩ).
Check whether the measuring device is damaged or contaminated. Check
whether the pressure hoses are not blocked. Replace the pressure sensor,
if necessary.
Check whether the measuring device is damaged or contaminated. Check
whether the pressure hoses are not blocked. Replace the pressure sensor,
if necessary.
Check whether the air quality sensor is connected correctly. Check function
of the sensor, if necessary (output signal value).
Check address and sensor value in BMS system. Check function of BMS
sensor.
Replace filter.
Automatic protection of water heater battery is active to prevent damage at
low temperatures. This function ends automatically as soon as the return
temperature has reached the target value.
Process ends automatically.
Process ends automatically.
Supply air temperature is not reached. There is an automatic power correc-
tion (supply air fan is adjusted down).
14
Solution