5.8 Alarm management

In an alarm/warning situation, follow the procedure below:
set
Press
to enter menu of direct parameters.
to fi nd parameter " AL " .
Use the arrows
or
set
Press
to see alarm code:
set
AL
HiSt
esc
.....
Hd
Alarm list
Cod.
Description
Ld
Low dew point
Lt
Low evaporation temperature
Ht2
High discharge temperature
HP
High pressure
LP
Low Pressure
PI
Compressor Thermal protection
PH
Inverted phases
Warning list
Cod.
Description
FB0
B0 sensor warning
FB2
B2 sensor warning
FB8
B8 sensor warning
FB5
B5 sensor warning
FPI
PI sensor warning
DrE
Condensate drain warning
Hd
High dew point warning
Ht1
High discharge temperature
HB5
High evaporator temperature
English
5.9 Storico allarmi
In an alarm/warning situation, to see the current and previous alarms
occurred, follow the procedure below:
set
to enter menu " HiSt " .
Press
set
Press
to enter parameters :
Menu
Code
HiSF
HiSP
HySC
HiSt
HySd
set
HySt
Reset
M
M
M
M
M
HiSt
M
M
Reset
5.10 Setting clock/date.
A
A
1. Press "
" "
A
"FrEE".
set
A
2. Press "
" to enter menu "Ai".
A
3. Press "
" to enter il menu "CL".
set
A
4. Press "
" to enter and view parameter "HOUr".
set
A
5. Press "
" until the screen fl ashes "HOUr".
A
6. Select the fl ashing parameter "HOUr"/"dAtE"/"4EAr" using "
A
" and press "
7. Change the fl ashing value using "
and press "
esc
8. Press "
" to return to the menu "FrEE".
Description
General alarm number
Alarm position
Alarm code
Alarm date
(if clock option is present)
Alarm hour
(if clock option is present)
set
HiSt
set
esc
HiSP
HiSF
HiSC
HiSd
", together at the same time to enter menu
set
" to enter.
"and "
" (up and down)
set
" to confi rm.
PSE 120-350
9. Press "
" "
" together to exit.
Fig.3
set
dr4
FrEE
Ai
FrEE
esc
4EAr
dAtE
set
set
18.20
2015
01.09
set
!
The memory of the "clock / date" has a maximum duration of
three days, so if the controller is left without power for more than
three days, the data set hour / month / year are lost.
Adjust the clock at the start up of the machine, and whenever nec-
essary.
CL
set
HOUr
set
5 sec.
HOUr
set
17.15
5/12

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pse 120Pse 140Pse 180Pse 220Pse 260Pse 300 ... Afficher tout

Table des Matières