Flue setup (continued) /
This flue gas cascade system can be used for cascade of 2, 3 or 4 GB162 appliances.
See for the dimensions the tables below.
Cette cascade de fumées peut être utilisée pour les cascades comprenant 2, 3 ou 4 appareils du type
GB162. Voir ci-dessous pour obtenir les dimensions.
Length L (0 - 4,000 ft Sea level) /
Longueur L (0-4.000 ft au-dessus du niveau de la mer)
L1
min
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
4 m (13 ft)
2 m (6.5 ft)
3 × 80 kW
–
10 m (33 ft)
4 × 80 kW
–
2 × 100 kW
7 m (23 ft)
2 m (6.5 ft)
3 × 100 kW
–
4 × 100 kW
–
L
max
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
44 m (144 ft)
50 m (164 ft)
3 × 80 kW
–
46 m (151 ft)
4 × 80 kW
–
2 × 100 kW
29 m (95 ft)
50 m (164 ft)
3 × 100 kW
–
4 × 100 kW
–
min
Length L (4,001 - 8,000 ft above sea level) /
Longueur L (4.001-8.000 ft au-dessus du niveau de la mer)
L1
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
8 m (26 ft)
2 m (6.5 ft)
3 × 80 kW
–
4 × 80 kW
–
2 × 100 kW
7 m (23 ft)
2 m (6.5 ft)
3 × 100 kW
–
4 × 100 kW
–
L
max
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
24 m (79 ft)
50 m (164 ft)
3 × 80 kW
–
4 × 80 kW
–
2 × 100 kW
29 m (95 ft)
50 m (164 ft)
3 × 100 kW
–
4 × 100 kW
–
L
= L1 + L2 + L3
max
L3
6 720 646 836 (2013/08)
agencement des tuyaux d'évacuation des fumées (suite)
L1
L1
L1
min
min
min
Ø250 (10")
Ø315 (12")
–
–
3 m (10 ft)
–
–
7 m (23 ft)
3 m (10 ft)
–
–
–
3 m (10 ft)
–
–
10 m (33 ft)
3 m (10 ft)
L
L
L
max
max
max
Ø250 (10")
Ø315 (12")
–
–
50 m (164 ft)
–
–
50 m (164 ft)
50 m (164 ft)
–
–
–
50 m (164 ft)
–
–
50 m (164 ft)
50 m (164 ft)
min
min
min
L1
L1
L1
Ø250 (10")
Ø315 (12")
–
–
–
3 m (10 ft)
–
–
10 m (33 ft)
3 m (10 ft)
–
–
–
3 m (10 ft)
–
–
10 m (33 ft)
3 m (10 ft)
L
L
L
max
max
max
Ø250 (10")
Ø315 (12")
–
–
–
50 m (164 ft)
–
–
50 m (164 ft)
50 m (164 ft)
–
–
–
50 m (164 ft)
–
–
50 m (164 ft)
50 m (164 ft)
L2
Length L (8,001 - 10,200 ft above sea level) /
Longueur L (8.001-10.200 ft au-dessus du niveau de la mer)
L1
L1
min
min
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
–
4 m (13 ft)
3 × 80 kW
–
–
4 × 80 kW
–
–
2 × 100 kW
–
5 m (16 ft)
3 × 100 kW
–
–
4 × 100 kW
–
–
L
L
max
max
A
Ø160 (6")
Ø200 (8")
2 × 80 kW
–
50 m (164 ft)
3 × 80 kW
–
–
4 × 80 kW
–
–
2 × 100 kW
–
50 m (164 ft)
3 × 100 kW
–
–
4 × 100 kW
–
–
>3˚
Flue cascade | Cascades des fumées GB162-(L.B.-)80 kW/100 kW
L1
L1
min
min
Ø250 (10")
Ø315 (12")
–
–
5 m (16 ft)
–
–
5 m (16 ft)
–
–
7 m (23 ft)
–
–
6 m (19 ft)
L
L
max
max
Ø250 (10")
Ø315 (12")
–
–
50 m (164 ft)
–
–
50 m (164 ft)
–
–
50 m (164 ft)
–
–
50 m (164 ft)
L1