Installation And Putting Into Service; Installation; Compressor Installation; Connections - MIL'S AM 3 Notice D'utilisation

Compresseurs à vis
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

 
3. INSTALLATION AND PUTTING INTO SERVICE 
3.1.
Installation 
 
CAUTION Observe safety instructions!  
Always stay away from the danger zone of a load being lifted! 
3.1.1. Compressor installation 
Keyword 
Instructions
Installation site 
Ground: even, horizontal, firm 
Check load carrying capacity of floor. 
Air: as cool, clean and free of frost as possible, as low humidity as 
possible Temp.: +3°C (37°F) ‐ +40°C (104°F) * 
Sufficient ventilation of compressor room 
Air intake must be unobstructed 
Place air intake opening in a position where loose objects cannot be 
drawn in.  
Ensure installation site has sufficient lighting (for reading of instruments, 
carrying out maintenance, etc.) 
Lifting work 
Secure all loose and swinging parts, before lifting the compressor. 
Use an appropriate lifting vehicle (weight according to data sheet) 
Always stay away from the danger zone of a load being lifted 
Pipelines, pressure lines 
Before assembling pipelines, remove all flanges, plugs, caps and sacks 
using a drying agent. 
Ensure that the pressure system can expand from the compressor to the 
aftercooler or air system due to heat. Make sure it does not come into 
contact with flammable materials. 
Exhaust 
Exhaust ducts must have a diameter at least equal to that of the cooler 
surface and should be 3m in max. length with one bow of 90°; for longer 
ducts, use an additional fan with a capacity 20% greater than the 
compressor ventilator 
When using multiple units, make sure no compressor can draw in the 
heated exhaust of another compressor. 
 
*in case the ambient temperature is higher, please consult your dealer or the manufacturer 
520513.01 
 
AM3 – AM55 
3.2.
Connections 
3.2.1. Compressed air connection 
The unit's piping has been installed ready for operative use.  
You must follow the following advice when connecting the unit to the compressed air system:  
Keyword 
Instructions
Pressure 
Connection 
Shut‐off valve 
Condensate 
 
The unit must only be connected by an electrician 
Observe the following when connecting the unit to the mains 
3.2.2. Electrical diagram 
See annex 
3.2.3. Electrical connections 
The unit has been wired so as to be ready for immediate use. You only need to connect the unit to the mains.  
 
Keyword 
Instructions
Voltage 
Direction of rotation
Fuses
Connection 
Attention: Do not use plug if it's possible 
 
Use fittings and pipe lines suitable for the operating pressure.  
Do not operate the unit at a final pressure greater than that specified on 
the name plate 
A check valve between the unit and the compressed air system is not 
necessary as one has already been installed in the unit itself. 
Connect unit to the compressed air system stress‐free, and free from 
vibration (via a flexible hose for ex.)  
We recommend you also install a shut‐off valve to enable you to carry out 
maintenance work on the compressor without having to remove pressure 
from the compressed air system. 
An automatic condensate drain can be installed after the aftercooler to 
remove condensation from the compressed air 
Only connect the unit to the supply voltage specified on the name plate of 
the motor. 
Follow correct direction of rotation! Anticlockwise when viewed from the 
front. 
Checking the rotational direction see chap. 3.3/3.4. Not necessary for 
frequency‐controlled compressors 
A primary fuse and master switch with EMERGENCY‐STOP function must be 
installed by the Operating Company. The switch must have a capacity at 
least 1.1 times the rated output of the motor and must be uniquely 
assigned to the unit. 
Ensure that the electrical network is sufficiently fused (see data sheet) 
Lay the supply cable safely so that  
people cannot trip over it. 
Lead the cable with the wires L1, L2, L3, N and PE through corresponding 
screw  fittings (we do not recommend to use plugs) into the connection 
cabinet. 
Connect the wires to the appropriate terminals L1, L2, L3, N and PE 
 
22 

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Am 4Am 5Am 7Am 11Am 15Am 18 ... Afficher tout

Table des Matières