IFM Electronic AS-interface AC2503 Notice De Montage page 7

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Infrared addressing
The AS-i module also offers the option of infrared addressing with the
addressing unit AC1144.
The AS-i communication (yellow cable) must be switched off
during the infrared addressing. To do so, disconnect the master.
Supply the slaves with voltage via the AS-i power supply. Addressing is
carried out via the IR addressing cable E70211.
When the ifm AS-i power supplies SL are used the communication can
be deactivated via a plug on the power supply.
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED 1 yellow:
• LED green:
• LED 2 red is lit:
• LED 2 red flashing:
• LED 3:
Overload and short circuit of the input supply are signalled to the
AS-i master (version 2.1) via the "peripheral fault" flag in the sta-
tus register.
output switched
voltage supply o.k.
AS-i communication error, slave does not
participate in the "normal" data exchange,
e. g. slave address 0
peripheral fault, e.g. overload or short cir-
cuit of the sensor supply
infrared reciever
7
PAGE

Publicité

Table des Matières
loading

Table des Matières