ModBus-register W3 applies to software after 1.12
Input register
16 bit integer register
Modbus
Name
3x0001
Component Name ID
3x0002 - 0017
Component Name
3x0018
Applacation ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot (Hours)
3x0027
Time since last boot (Minutes) 0/60
3x0028
Temp sensor regulator
3x0029
Temp sensor RU1
3x0030
Temp sensor RU2
3x0031
Temp set point RU
3x0032
Flow set point RU
3x0033
Battery level RU
3x0034
Not used
3x0035
Not used
3x0036
Not used
3x0037
Input Analog 1
3x0038
Input Analog 2
3x0039
Input Analog 3
3x0040
Input Analog 4
3x0041
Output PWM 1
3x0042
Output PWM 2
3x0043
Output PWM 3
3x0044
Output PWM 4
3x0045
Output Analog 1
3x0046
Output Analog 2
3x0047
Output Analog 3
3x0048
Output Analog 4
3x0049
PID Water Out
3x0050
PID ChangeOver Out
3x0051
Not used
3x0052
Not used
3x0053
Cool Water
3x0054
Warm Water
3x0055
SA Damper pos.
3x0056
EA Damper pos
Read only
Min/Max
Remarks
0/10
ID for type of controller in Conductor and
Wise system
0/999
Name built of max 16 chr, exch chr (ASCII
standard)
0/8
0=Init, 1=Auto Normal, 2=Auto Economy,
3=AutoBoost, 4=Manual, 5=TimerFunction,
6=Stand-by, 7=Emergency, 8=NightCool
0/8760
After 8760h Year is updated
After 60min Hour is updated
Cels. Scaling 1:10
Cels. Scaling 1:10
Cels. Scaling 1:10
Setpoint in regulator form parameter or
Room Unit
Volts. Scaling 1:10
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
-100/100
(%)
-100/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
Service
Default
5 : 63