Swegon W1 Manuel Technique page 56

Table des Matières

Publicité

Service
ModBus-register W1 applies to software after 1.12
Holding
16 bit integer register
register
Modbus
Name
4x0037
Not used
4x0038
Not used
4x0039
Not used
4x0040
Not used
4x0041
Not used
4x0042
Not used
4x0043
Not used
4x0044
Not used
4x0045
Not used
4x0046
Not used
4x0047
Not used
4x0048
P term Heat
4x0049
I term Heat
4x0050
P term Cool
4x0051
I term Cool
4x0052
P term Change over
4x0053
I term Change over
4x0054
Not used
4x0055
Not used
4x0056
Not used
4x0057
Not used
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
4x0064
Not used
4x0065
Not used
4x0066
Not used
4x0067
Not used
4x0068
Not used
4x0069
Copy of Coil Status 1-16
5 : 56
R/W
Min/Max
Remarks
10/10000
Scale 1:100
10/10000
Scale 1:100
10/10000
Scale 1:100
10/10000
Scale 1:100
10/10000
Scale 1:100
10/10000
Scale 1:100
0-50
(degC) Only used in Manual state
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
...
Bit15=0x0016"
Default
3500
10
3500
10
5000
50