Safety instructions

2.1

Principles

The operations shall be carried out
by qualified electricians or suitably
trained personnel according to
IEC/EN 60079-14 and engineer-
ing/development specialists
according to IEC/EN 60079-0.
The empty enclosure type S-TB are not
suitable for Zone 0 and Zone 20 hazardous
areas.
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered by the user.
They shall be used for their intended purpose
and in perfect and clean condition.
After the empty enclosure type S-TB has been
installed, it shall be tested and fully certified
by a testing authority or authorized person.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in italics
the same as this text!

2.2 Legend

Safety warning
Note
This symbol highlights important informa-
tion.
X
Special conditions
ATEX - IEC
This symbol shows Highlights for safe use in
accordance to EU-Type-Examination Certificate/
IEC Ex-Certificate of Conformity.
3

Conformity with standards

The empty enclosure type S-TB has been
designed, manufactured and tested by Cooper
Crouse-Hinds (CCH), according to the state of
the art and to DIN EN ISO 9001 and
EN ISO/IEC 80079-34.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
Explosion-protected empty enclosure
made of stainless steel type S-TB
1

Technical data

1.1 Empty enclosure type S-TB

ATEX type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
IECEx type examination certificate:
Category of application:
IEC60079-0
Permissible service temperature
*
If the brass through bolt is used with a washer, the maximum operating temperature is reduced to 65°C.
Perm.storage temperature in original packing
Protection category acc. to IEC/EN 60529
Dimensions:
Test torques:
Cover screws:
Gland plate screws:
4

Field of application

Fully certified empty enclosures that have
been tested by a testing authority or
authorized person are suited for use
in hazardous areas in Zone 1/2 and
Zone 21/22 in accordance with
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The enclosure materials employed, including the
exterior metal parts, are made of high-quality
materials which ensure a corrosion protection
and resistance to chemical sub-stances
corresponding to the requirements in a "normal
industrial atmosphere":
- special stainless steel
- brass
- plastic
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
BVS 13 ATEX E 015U
II 2 G Ex e IIC Gb
II 2 G Ex e IIB Gb
II 2 D Ex tb IIIC Db
IECEx BVS 13.0025U
Ex e IIC Gb
Ex e IIB Gb
Ex tb IIIC Db
depends on sealing material of the enclosure:
see chapter 10.1
-20 °C to +40 °C
IP 66
(catalogue version)
see last page
4,0 Nm
2,0 Nm
5

Use / Properties

The fully certified empty enclosure type
S-TB that has been tested by a testing authority/
authorized person is used for the distribution of
electric energy e.g. light circuits, heating
circuits, control circuits, intrinsically safe circuits
etc. (see technical data for temperature class,
explosion group, permissible ambient temperature).
The data as per point 3 and 4 shall be taken
into account with the use.
The responsibility for the suitability and
proper use of the empty enclosure
type S-TB lies with the user.
X
The operation temperatures of the sealing
ATEX - IEC
materials have to be taken into account for the
certification of the complete equipment.
X
The creepage and clearance distances in
ATEX - IEC
the enclosure have to be taken into account for
the copmlete electrical equipment.
X
The painted empty enclosure type
ATEX - IEC
S-TB P * ** ** ** * * SL * **** may only be
used in areas with potential explosive dust
atmospheres if high or repeated charging
processes (e.g. air ions in the vicinity of high volt-
age electrodes, high speed flowing liquids and
pneumatic transfer of powders, and paper or
plastic foils transported by machines) are surely
excluded. Manual rubbing is not considered to
be a high charging process.