Safety Instructions - LEGRAND Alpes Technologies ALPIMATIC/BX Guide D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
 The automatic capacitor banks must be installed in accordance with the installation instructions
described in the manuals. If they have suffered any external knocks or blows, do not connect or use
the capacitors or capacitor banks.
Incorrect installation and use may lead to the risk of electric shock or fire. Capacitor banks must be
used in normal conditions, in other words they must not be subjected to any other
Voltage/Current/Frequency/Harmonic distortion/Temperature values than those specified in the sales
catalogue and manual.
 Only use accessories recommended by the Legrand Group in the sales catalogue and manuals.
 As we are keen to ensure the highest levels of performance of our products, they may be subject to
modification. Please check the accuracy of the product specifications during installation and
commissioning operations, and refer to the relevant manuals. If you have any questions or need any
clarification, please contact your Legrand Group representative.
 Installation, use and maintenance of an automatic capacitor bank must only be undertaken by trained
and authorised staff, in accordance with the regulations in force specific to each country.
 Any modification of the automatic capacitor banks which has not previously been authorised
by the Legrand Group voids all liability, replacement rights and warranties.
 Wear the necessary PPE (personal protective equipment) when working on live products.
 Comply with the safety procedures associated with electrical work.
 Inappropriate electrical and mechanical use of equipment can be dangerous and can result in
physical injury or material damage.
 Ensure that the automatic capacitor banks are correctly earthed.
 Switch off all the capacitor bank power supplies before working on it.
 Before working on live parts, wait at least 5 minutes for the capacitors to discharge, then short-circuit
the terminals and earth the capacitor.
 During operations involving access inside the capacitor bank, beware the risk of burns when touching
the products or metal parts (during operation or just after the capacitor bank has been switched off).
 Before restoring power to the capacitor bank, check that all the physical protection devices have
been replaced (for example: shield, cover, door).
 Any failure to follow procedures and warnings to the letter can lead to premature failure,
explosion, or an outbreak of fire in the equipment.
_____________________________________________________________________________________________________
1 – SAFETY INSTRUCTIONS
Risks of electric shocks, burns and explosion
General
29

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières