C – AUXILIARY CIRCUITS
Your capacitor bank is guaranteed to work if the following equipment is connected:
Current transformer (CT)
Generator load shedding
Safety kit
The ancillary equipment is connected to a set of terminal blocks:
Characteristics
Power: 600 VA max.
Cable cross-
section
Terminals
(1)
When there is a generator on the internal supply.
(2)
Not included in 770 mm high enclosures without reactors, in version with circuit breaker with power ≤ 125 kVAr, in version
without circuit breaker with power ≤ 150 kVAr.
(3)
Please refer to page 31 for more information.
_____________________________________________________________________________________________________
(1)
(2)(3)
Safety kit
NC contact
Consumption: 10.5 W
2.5 mm²
X1/X2
Generator set
Terminal for load-
shedding contact
2.5 mm²
G/E
38
Current transformer
Current input: 1 A or 5 A
Power: 10 VA min.
Class 1
2.5 mm² to 6 mm²