KEB Combivert F5 Manuel D'installation page 43

Variateur de fréquence
Masquer les pouces Voir aussi pour Combivert F5:
Table des Matières

Publicité

Annexe B
Variateur
05F5
05F5
07F5
07F5
05F5
07F5
09F5
*) The voltage rating of the Class rated fuses (CC,J or RK5) shall be at least equal to the
voltage rating of the Drives.
Branch Circuit Protection: Type E Self Protected Manual Motor Controllers for
inverters F5-A housing.
Cat. No.
05F5
05F5
07F5
07F5
Tension d'entrée
[V]
240 / 1ph
240 / 1ph
240 / 1ph
240 / 1ph
400 480 / 3ph
400 480 / 3ph
400 480 / 3ph
Drive Input
Self Protected Manual Motor
ating
Controller Type and manufac-
240V/ 1ph
PKZMO-10E, Eaton Industries
240V/ 3ph
PKZMO-6.3E, Eaton Industries
240V/ 3ph
PKZMO-16E, Eaton Industries
240V/ 1ph
PKZMO-10E, Eaton Industries
UL 248 Fuse Class
J or RK5 *
[A]
10
6
15
10
5
6
10
turer
UL 248 Fuse Class
CC *)
[A]
10
5
20
10
---
---
---
Self Protected Manual
Motor Controller rating
230V, 1.5 hp
230V/3ph, 1.5 hp
230V, 2 hp
230V/ 3ph, 3 hp
F - 43

Hide quick links:

Publicité

Table des Matières
loading