Operating Instructions
Transducer for AC voltage DVT-XXXA
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then ..................................................... 6
2. Brief description .......................................................... 6
3. Technical data ............................................................. 6
4. Mounting ..................................................................... 6
5. Electrical connections ................................................. 7
6. Commissioning and maintenance ............................... 7
7. Releasing the transducer............................................. 7
8. Instruments admissions .............................................. 7
9. Dimensional drawing ................................................... 8
10. Declaration of conformity ............................................ 8
1. Read first and then ...
The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully and the safety warnings given
in the various Sections

4. Mounting

5. Electrical connections are
observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.
Unauthorized repair or alteration of the unit invalidates
the warranty!

2. Brief description

The transducer DVT-XXXA is designed to convert a sinusoidal
AC voltage into a DC current or voltage signal proportional
to the measured value. It does not require a separate power
supply.

3. Technical data

Measuring input
Nominal frequency:
50/60 Hz
Nominal input voltage: Please note the max. input voltage
on the type label!
0 - 20 to 0 - 600 V
Own consumption
at nominal
frequency 50 Hz:
2.0 VA with 20 mA output
1.6 VA with 10 mA output
1.4 VA with 5 mA output
1.2 VA with 1 mA output
7004-00063-A Rev --.indd
Setting
(special feature):
Measuring output
DC current:
Burden voltage:
External resistance:
DC voltage output
not superimposed:
External resistance:
Time response:
Accuracy (acc. to IEC 688)
Reference value:
Basic accuracy:
Input:
Temperature influence
(- 10 to + 55 °C):
Safety
Pollution degree:
Installation category:
Environmental conditions
Operating temperature: -10 to + 55 °C
Storage temperature:
Relative humidity
of annual mean:
Altitude:
Indoor use statement
4. Mounting
The DVT-XXXA can be mounted on a top-hat rail.
Note "Environmental conditions" in Section
"3. Technical data" when determining the place
of installation!
Page 6 of 8
Admissible alteration of full scale out-
put, variable sensitivity, adjustable
with potentiometer (see fig. 3)
Setting range approx. 0.9 - 1.1 · U
(approx. ± 10%)
U
N
100%
0
0
Meas. input
0.9
0-1, 0-5, 0-10 or 0-20 mA
15 V
See Section "5. Electrical connec-
tions"
0 - 1 to 0 - 10 V
See Section "5. Electrical connec-
tions"
≤ 300 ms
Input end value
Class 0.5
20 - 100%
0.2% / 10 K
2
III (at ≤ 300 V)
II (at > 300 V)
- 40 to + 70 °C
≤ 75 %
2000 m max.
8/12/09
N
1
1.1