Installation and Operating Instructions
m
NOTE
CHAPTER 3
TECHINCAL DATA
Flat EC Centrifugal Fan Boxes – SlimVent SV.. EC ...
2.4
Storage
When storing for a prolonged time, the following steps are to be taken to avoid damaging influences: Motor protection
by dry, airtight and dust-proof packaging (plastic bag with desiccant and humidity indicators). Vibration-free, watertight
and constant-temperature storage at a temperature in the range -20 °C to +40 °C.
In case of a storage period of more than three months or motor standstill, maintenance must be carried out before
commissioning according to chapter 8. In case of reshipment (above all, over longer distances; e.g. by sea), it must be
checked whether the packaging is suitable for the form and route of transport. Damages due to improper transportati-
on, storage or putting into operation are not liable for warranty.
2.5
Performance data
The unit type plate gives an indication of the mandatory electrical values; which must be coordinated with the local
supply network. The fan performances* were established on a test stand according to DIN EN ISO 5801.
2.6
Noise data
Noise data that refers to certain distances apply to free field conditions. With regard to installation, the sound pressure
level can differ significantly from the catalogue data, as it is highly dependent on the installation conditions, i.e. on the
absorption capability of the room and the room size among other factors.
2.7
Air flow direction and direction of rotation
The fans have a fixed direction of rotation and air flow direction (they are not reversible), which are marked on the units
with arrows (direction of rotation red, air flow direction blue). The air flow direction can be set through the installation.
2.8
Protection against contact
- SlimVent SV.. EC ... are not delivered with fan protection guards as standard. Depending on the installation conditions,
protection against contact may be necessary on the suction and/or discharge side. Corresponding protection guards are
available as accessories.
- Fans which are protected by their installation method (e.g. installation in ventilation ducts or closed assemblies) do
not require protection guards if the plant provides the necessary level of safety. Please note that the operator is
responsible for complying with the current standard and can be held liable for accidents as a consequence of missing
protection systems.
2.9
Motor protection
All SlimVent EC fans are equipped with an integrated electronic temperature monitoring system for the
EC motor and the electronics system. This system protects the motor from overloading and overheating.
m
If the thermal contacts are triggered frequently (standstill), the fan must be inspected by a specialist accor-
ding to chapter 1.4.
2.10 Condensation
If the fan is used intermittently, especially in a humid and warm environment, or if variations in temperature occur, con-
densation may build up in the motor and draining off must be ensured. In case of condensation in the ducting and fan
casing appropriate measures must be taken during installation (water sack, drainage line). Under no circumstances
must the motor come into contact with water.
3.0
SlimVent SV.. EC ... type overview
A
330
SVR EC 100
330
SVR EC 125
390
SVR EC 160 A
390
SVR EC 160 B
390
SVR EC 200
389
SVR EC 250
444
SVR EC 315
Dimensions in mm
B
C
D
E
F
314
138
ø100
310
61
314
163
ø125
310
73
362
198
ø160
368
91
362
198
ø160
368
91
372
238
ø200
368
111
392
271
ø250
676
135
427
337
ø315
788
168
3
SlimVent – Flat EC Centrifugal Fan Box
with variable speed control
Series
SVR EC 100
SVR EC 125
SVR EC 160 A
SVR EC 160 B
SVR EC 200
SVR EC 250
SVR EC 315
Energy-efficient, backward-curved high per-
formance centrifugal impeller
G
48
48
48
48
48
48
48
EN
Ref. no. 6124
Ref. no. 2531
Ref. no. 2535
Ref. no. 2543
Ref. no. 2539
Ref. no. 2294
Ref. no. 2669