Recommended Tools; Required Materials Per Frame; Introduction To System Hardware; Leviton Hdf3168 Mda Frame System Components - Leviton HDF3168 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.7

Recommended Tools

The following tools are recommended for successful installation of the HDF3168 Frame and components.
1. Hammer Drill
2. 5/8" masonry drill bit
3. #2 Philips screw driver with minimum 8" shaft and magnetic tip
4. Socket set
5. 1/2" Torque wrench
6. Hand or electric saw with metal blade
For Raised Floor installations add:
7. 5/8" Hardened Steel Drill Bit
8. Plumb Bob and string
9. Universal step bit
1.8

Required Materials per Frame

The following materials are required for successful installation of the HDF3168 Frame and components.
(Listed materials are not included in Leviton provided HDF3168 products. Quantities below are the
minimum required and may vary depending on the actual mounting environment)
1. (4) 5/8" diameter 1/2" x 13 thread Hex Head Anchors
2. (4) 1/2" x 13 Thread Bolts (when direct to concrete slab)
3. 1/2" Threaded Rod (when mounted on Raised Access Floor)
4. (4) 1/2" Split Lock Washers
5. (4) 1/2" Fender Washers
6. (4) 1/2" x 13 Thread Nuts
7. Velcro Tie wraps (recommended bulk rolls – example Leviton #43115-075)
2.

Introduction to System Hardware

The Leviton HDF3168 MDA Frame system hardware can be divided into five major classifications. These
are:

Leviton HDF3168 MDA Frame System Components

Leviton HDF3168 MDA Frame Connectivity Components
Leviton HDF3168 MDA Frame Cross Frame Routing Components
Leviton HDF3168 MDA Frame Enclosure Components
2.1
Leviton HDF3168 MDA Frame System Components
The System Components are:
A. MDA High Density Frame
The frame is an 84" high x 24" wide x 20.4" deep equipment frame designed to fit within a 24" x
24" space. The frame allows for the placement of any combination of up to 22 Patch decks,
Splice Decks, Cross Frame Routing Trays or Blank Plates. The frame can either be mounted
directly to the structural floor or on Raised Access Floor.
DI-000-F3168-20B
Leviton HDF3168 Fiber Distribution System User Guide
9

Publicité

Table des Matières
loading

Table des Matières