Planning the System Installation

A single Leviton HDF3168 MDA Frame may serve as the mounting location for up to twenty-two (22)
Decks. Decks are available as either Patch Decks (six trays per deck) or Splice Decks (three trays per
deck). Cable Routing trays can replace decks at any mounting location within a frame as needed.
Tip: =
For best results, Leviton recommends the use of:
2.0mm or smaller diameter patch cords with round cord or 1.6mm zipcord
construction. LC patch cords are recommended to utilize duplex uniboot
connectors.
Leviton Micro Data Center Plenum reduced diameter trunks. The use of Micro Data
Center trunk cabling is required for 24-strand MTP configurations.
Trunks and Patch Cords designed specifically for the HDF 3168 system can be selected in
our product configurators at www.leviton.com/HDF3168.
HDF3168 MDA Frames require a 2' x 2' area. If installing on a Raised Access Floor the tiles in front of
and behind the Frame should be accessible in order to route trunk cabling. Cable pathways should be
mounted above and/or below the HDF3168 MDA Frame as would be typical of other Equipment Racks
and Cabinets. Recommended spacing from walls or other rows of equipment racking is as follows:
From walls – minimum 1inch side, minimum 3 feet front or rear.
From adjacent rows - minimum 3 feet, 4 feet recommended in Cold Aisles per TIA 942.
The Following is an example of 3 HDF3168 MDA Frames mounted without Front Door kits in Plan View
(Figure 7).
DI-000-F3168-20B
Leviton HDF3168 Fiber Distribution System User Guide
15