Planning For Updating Existing Mda Or Hda Installations - Leviton HDF3168 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Figure 7
3.1

Planning for Updating Existing MDA or HDA Installations

First, see the entire discussion (above) about planning for new installations, then see additional
suggestions below.
When planning to install Leviton HDF3168 MDA Frame as an upgrade, the planner needs to evaluate the
cables, connectors, polarity method* and hardware in the existing installation (patch panels and cable
management). HDX High Density cassettes and adapter plates can be interchanged or replaced to
provide migration from 10G to 40G or 100G.
The following are maximum recommended capacities for each HDF Frame by connector type: 40G and
100G systems are only recommended to use 18 Deck Units due to high trunk counts and associated
cable management limitations.
DI-000-F3168-20B
Leviton HDF3168 Fiber Distribution System User Guide
Number
of
Connector type
Decks
LC
22
SC
22
MTP
18
MTP
18
Maximum
Strands per
Frame
3,168 w/12
strand MTP
1,584
7,776 w/12
strand MTP
15,552 w/24
strand MTP
16

Publicité

Table des Matières
loading

Table des Matières