Piping Works and Flaring technique
• Do not use contaminated or damaged copper tubing. If
any piping, evaporator or condenser had been exposed
or had been opened for 15 seconds or more, the system
must be vacuumed. Generally do not remove plastic,
rubber plugs and brass nuts from the valves, fi ttings,
tubing and coils until it is ready to connect suction or
liquid line into valves or fi ttings.
• If any brazing work is required, ensure that nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation
on the inside wall of copper tubings.
• Cut the pipe stages by stages, advancing the blade of
pipe cutter slowly. Extra force and a deep cut will cause
more distortion of pipe and therefore extra burr. See
Figure I.
• Remove burrs from cut edges of the pipes with remover.
See Figure II. Hold the pipe on top position and burr
removel at lower position to prevent metal chips from
entering the pipe. This will avoid unevenness on the
fl are faces which will cause gas leak.
• Insert the fl are nuts, mounted on the connection parts
of both the indoor unit and outdoor unit, into the copper
pipes.
• The exact length of pipe protruding from the top surface
of the swaging block is determined by the fl aring tool.
See Figure III.
• Fix the pipe fi rmly on the swaging block. Match the
centers of both the swaging block and the fl aring punch,
then tighten the fl aring punch fully.
• The refrigerant pipe connection are insulated by closed
cell polyurethane.
Piping Connection To The Units
• Align the center of the piping and tighten the fl are nut
suffi ciently with fi ngers. See Figure IV.
• Finally, tighten the fl are nut with torque wrench until the
wrench clicks.

REFRIGERANT PIPING

• When tightening the fl are nut with the torque wrench,
ensure that the tightening direction follows the arrow
indicated on the wrench.
• The refrigerant pipe connection are insulated by closed
cell polyurethane.
Pipe Size, mm (in)
6.35 (1/4")
9.52 (3/8")
12.70 (1/2")
15.88 (5/8")
19.05 (3/4")
Figure I
Figure II
Figure III
Swaging Block
Ø Tube, D
Inch
1/4"
6.35
3/8"
9.52
1/2"
12.70
5/8"
15.88
3/4"
19.05
Figure IV
1-11
Torque, Nm / (ft-Ib)
Cutting Copper Tube
1/4t
Remove Burr
Copper Tube
D
A (mm)
mm
Imperial
(Wing-nut Type)
1.3
1.6
1.9
2.2
2.5
Flare Joint
Flared Tube
Indoor Piping
Torque Wrench
Spanar
18 (13.3)
42 (31.0)
55 (40.6)
65 (48.0)
78 (57.6)
Rigid
(Clutch Type)
0.7
1.0
1.3
1.7
2.0
Flare Nut