Item 1
Code for voltage and No. of poles
acc. to IEC
Voltage
2-pole + PE
110 - 130V 50/60Hz
200 - 250V 50/60Hz
3-pole + PE
200 - 250V 50/60Hz
480 - 500V 50/60Hz
380 - 415V 50/60Hz
600 - 690V 50/60Hz
3-pole + N + PE
480 - 500V 50/60Hz
380 - 415V 50/60Hz
600 - 690V 50/60Hz
Plug and socket system 32A, GHG 522
6.3
Cable entries (KLE);
Item 3
Item 4
blanking plugs
6.3.1
Plug and socket
Flexible cables shall be used with trumpet-
shaped cable glands or other suitable
entries with additional pull-relief.
When using cable entries with a lower IP
Item 2
protection than that which applies to the
device (see page 7, technical data), the IP
protection of the whole device will be reduced.
The mounting directives applicable to the
cable entries used shall be observed.
Unused holes shall be closed with a blanking
plug in order to establish the minimum
protection category.
In case of sealing inserts that are cut out, it
shall be ensured that the insert is properly
adapted to the cable diameter. Care has to be
taken that when fitting the cable entries,
sealing inserts appropriate to the cable
diameter are used.
In order to ensure the required minimum
protection category, the cable glands are to
be tightened down.
Overtightening might impair the protection
category.
All vacant metric CEAG cable entries shall be
closed with the certified blanking plug for
metric cable entries.
6.3.2
Plug
Fig. 9: In general, only the sealing inserts
fitted in the plug may be used. When
mounting the cable, attention has to be paid
that sealing inserts matching the cable
diameter be used. After having connected the
cable, the coupling ring item 2 is to be
screwed fingertight until the sealing effect is
obtained. Then the screws item 4 of the pull-
relief, item 3, are to be tightened down.
Clock
Mind! Overtightening might impair the pull-
face
relief effect!
Colour (PE)
yellow
4 h
blue
6 h
6.4

Closing the device

blue
9 h
black
7 h
In order to ensure the required minimum
red
6 h
protection category, the cover screws, the
black
5 h
screws of the plug and of the coupler shall be
tightened down.
black
7 h
The screws of the plug and the coupler shall
red
6 h
be tightened down.
black
5 h
Overtightening might impair the protection
category.
Any foreign matter shall be removed from
the device.
6.5

Taking into operation

Prior to taking the apparatus into operation,
the tests specified in the relevant national
regulations shall be carried out. Apart from
that, the correct functioning and installation of
the apparatus in accordance with these
operating instructions and other applicable
regulations will have to be checked.
Check the plug for any damages before
putting it in the socket.
The user must ensure that a uniform
equipotential earth applies throughout when
the plug and socket system is operated.
The inappropriate installation and
operation of the plugs and sockets can
entail the loss of warranty.
7

Maintenance/Servicing

Before opening the enclosure, make sure
that the device is disconnected from the
voltage, or take appropriate protective
measures.
The required maintenance intervals depend on
the specific application and will therefore have
to be determined by the user dependent on
the conditions of use.
If during servicing, repairs prove to be
necessary, section 8 of these operating
instructions will have to be observed.
8
Repair/Overhaul/
Modifications
Repairs and overhaul may only be carried out
with genuine CCH spare parts.
Modifications to the device or changes of
its design are not permitted.
9

Disposal/Recycling

When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed. In order to
facilitate the recycling of individual
components, plastic parts are provided with
the identification mark of the plastic material
used.
Subject to modifications or supplement of the
product range
Cooper Crouse-Hinds GmbH
10
10
10
10
10

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ghg 522 74

Table des Matières