Technical Data; Plug And Socket Ghg 522 - CEAG GHG 522 44 Mode D'emploi

Fiches et prises de 32 a
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
X = fixing dimensions
Wall socket without switch, 3- and 4-pole
Wall socket without switch, 5-pole
Wall socket with switch, 3- and 4-pole
Wall socket with switch, 5-pole
Plug, 3-pole
Plug and socket system 32A, GHG 522
1

Technical data

1.1
1.1

Plug and socket GHG 522

Plug and socket GHG 522
1.1
1.1
1.1
Plug and socket GHG 522
Plug and socket GHG 522
Plug and socket GHG 522
Rated voltage 3-pole
Rated voltage 4- and 5-pole
Rated current:
Back-up fuse:
without thermal protection
Switching capacity:
Wall socket with switch
Perm. ambient temperature:
(Special versions permit deviating temperatures)
Perm. storage temperature in original packing:
Protection category acc. to EN 60529 / IEC 529
with closed and secured hinged cover:
Insulation class acc. to EN 60598/IEC 598:
Cable entries:
Wall socket with switch
Wall socket without switch
Plug / Coupler 3-pole
Plug / Coupler 4- and 5pole
Supply terminal:
Wall socket with switch
Wall socket without switch
Flange socket / Coupler
Plug
Test torques:
Cap nut of the M40 entry
Cover screws
Terminals
Self-cutting screws size 4
Self-cutting screws size 5
Switch connection screw
Weight:
Wall socket without switch
Wall socket with switch
Plug
Flange socket
Inlet
Wall socket without switch
Wall socket with switch
Plug
Flange socket
Inlet
Wall socket without switch
Wall socket with switch
Plug
Flange socket
Flange socket, 3- and 4-pole
Plug, 4-pole
up to 415 V, 50/60 Hz
up to 690 V, 50/60 Hz
max. 32A
max. 32A
AC 23
AC 22
-20°C up to +40°C (catalogue version)
-55° C to +80° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1x M40 (Ø17-28mm) + 1x blanking plug M40
4x drilling M25 (2x top / 2x bottom)
incl. 1x enlargement gland M32 (Ø12-21mm)
Ø 12 - 21 mm
Ø 12 - 28 mm
Cross section
2 x 2.50 - 6 mm²
2 x 2.50 - 10 mm²
2 x 2.50 - 10 mm²
1 x 1.00 - 6 mm²
5,0 Nm
2.5 Nm
2.5 Nm
2.0 Nm
3.0 Nm
0.8 Nm
(catalogue version)
3-pole
GHG 522 23
3-pole
GHG 522 43
3-pole
GHG 522 73
3-pole
GHG 522 83
3-pole
GHG 522 93
4-pole
GHG 522 24
4-pole
GHG 522 44
4-pole
GHG 522 74
4-pole
GHG 522 84
4-pole
GHG 522 94
5-pole
GHG 522 25
5-pole
GHG 522 45
5-pole
GHG 522 75
5-pole
GHG 522 85
Flange socket, 5-pole
Cooper Crouse-Hinds GmbH
500V
690V
23 A
12 A
32 A
32 A
Stripped wire length
6 mm
12 mm
12 mm
10 mm
approx. 0.95 kg
approx. 2.05 kg
approx. 0.52 kg
approx. 0.49 kg
approx. 0.31 kg
approx. 1.00 kg
approx. 2.15 kg
approx. 0.60 kg
approx. 0.50 kg
approx. 0.32 kg
approx. 1.10 kg
approx. 2.25 kg
approx. 0.65 kg
approx. 0.51 kg
Plug, 5-pole
7 7 7 7 7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ghg 522 74

Table des Matières