The indoor unit must be installed in such a way so as to prevent
short circuit of the cool discharged air with the hot return air.
Please follow the installation clearance shown in the figure. Do
not place the indoor unit where there could be direct sunlight
shining on it. Also, this location must be suitable for piping
and drainage, and be away from doors or windows.
Air fl ow
(Indoor)
min. 50
Required space
(Space for
maintenance)
! CAUTION
Do not install the unit at altitude over 2000m.
Air Purging
To prevent pump damage, the fan coil unit should not be
energized until the coil and all water lines have been purged
of air.
The Air Vent located inside the casing. Removed the casing
and connect hose to the air vent while doing purging.
! CAUTION
Ensure there is no water droplets go into the control box
during purging process.

INSTALLATION DIAGRAM

CORK TAPE FULLY INSULATED
INSULATION THROUGH OUT CHILLED WATER PIPING

INSTALLATION OF THE INDOOR UNIT

min. 50
(Space for
maintenance)
All dimensions are in mm
The water piping can be routed to the unit in a number of ways
(left or right from the back of the unit), by using the cut-out
holes on the casing of the unit (see figure). Bend the pipes
carefully to the required position in order to align it with the
holes. For the side and bottom, hold the bottom of the piping
and then position it to the required direction (see figure). The
condensation drain hose can be taped to the pipes.
Right-side, right-back or right-bottom piping
Right-side piping
Remove pipe port cover here
for right-side piping
Remove pipe port cover here
for right-bottom piping
Left-side, left-back or left-bottom piping
Remove pipe port cover here
for left-bottom piping
1-4
Right-back piping
Right-bottom
piping
Bind coolant pipe
and drain hose
together with
insulating tape.
Remove pipe port
cover here for
left-side piping
Left-side piping
Left-back piping
Left-bottom piping