Installation Diagram - Daikin FTXK09P Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Indoor Unit
Front panel
1-15/16" (50mm) or more
from walls (on both sides)
Air fi lter
• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airfl ow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200mm) or less.
Wall facing one side
More than 1-15/16 (50)
47-1/4
(1200)
or less
Side View

INSTALLATION DIAGRAM

2-3/16" (55mm) or more from ceiling
M4 x 12L
 Opening service lid
Service lid is removeable.
 Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Outdoor Unit
INSTALLATION OF THE OUTDOOR UNIT (09/12)
More than 3-15/16 (100)
Caulk pipe
hole gap
with putty.
Service lid
Wall facing two sides
More than
3-15/16 (100)
More than 1-15/16 (50)
Wall facing three sides
More than 1-15/16 (50)
Top View
1-7
Cut thermal insulation pipe to an
appropriate length and wrap it with
tape, making sure that no gap is left
in the insulation pipe's cut line.
Wrap the insulation pipe
with the fi nishing tape
from bottom to top.
More than
5-7/8 (150)
More than 1-15/16 (50)
Top View
More than 5-15/16 (150)
More than 11-13/16 (300)
Unit : Inch (mm)