Indoor Unit
Air Discharge Louver
Preliminary Site Survey
Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must
•
be independent of welding transformers which can cause high supply fluctuation.
•
Ensure that the location is convenient for wiring, piping and drainage.
•
The indoor unit must be installed in such that is free from any obstacles in path of cool air
discharge and warm air return, and must allow spreading of air throughout the room (near the
center of the room).
•
Must be provide clearance for the indoor unit from the wall and obstacles as shown in the
figure.
Obstacle
•
The installation place must be strong enough to support a load 4 times the indoor unit weight to
avoid amplifying noise and vibration.
•
The installation place (hanging ceiling surface) must be assuring levelness and the height in the
ceiling is 350mm or more.
•
The indoor unit must be away from heat and steam sources (avoid installing it near an
entrance).
1 IM 5CKC-0912(0)DAIKIN-EN.indd 6
1 IM 5CKC-0912(0)DAIKIN-EN.indd 6
INSTALLATION DIAGRAM
Drain Piping
Front Panel
Air Filter
(behind the grille)
Air Intake
Air Discharge
INSTALLATION OF THE INDOOR UNIT
0.5m or more
0.5m or more
Floor
Thermal Insulation
Wrap the insulated pipe
with the finishing tape
from bottom to top
Air Intake Grille
Air Intake
1-6