Koudwater-Ventilatorluchtkoeler Manual de instalación Español Unidades De Serpentín De Ventilador De Agua Fría Models Manuale Di Installazione Italiano Unità Fan Coil Ad Acqua Fredda FWC07AATNMV1 FWC08AATNMV1 Εγχειρίδιο εγκατάστασης Ελληνικά Μονάδες Πηνίου Του Ανεμιστήρα Υια Το Παγωμένο Νερ FWC10AATNMV1 FWC11AATNMV1 Portugues Manual De Instalação...
OUTLINE AND DIMENSIONS Indoor Unit: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 SEE DETAIL A DETAIL A WATER OUTLET WATER INLET All dimensions are in mm. SAFETY PRECAUTIONS ! WARNING ! CAUTION Please take note of the following important points when •...
INSTALLATION OF THE INDOOR UNIT 1. Preliminary Site Survey Min. 0.5 m Min. 0.5 m Min. 0.5 m Obstacle Floor • Electrical supply and installation is to conform to local authority’s (e.g. National Electrical Board) codes and regulations. • Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fluctuation.
Page 5
5. Drain Test • Connect the main drain pipe to the flexible drain. Feed Water • Feed water from flexible drain hose to check the piping for leakage. • When the test is completed, connect the flexible drain hose to the Main Drain Pipe drain connector on the indoor unit.
ELECTRICAL WIRING CONNECTION This is proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national code and regulations. Model: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2...
OPERATING RANGE Operating Limits: Thermal carrier : Water Water temperature : 5 ~50°C Maximum water pressure : 16 bar Air temperature : (as below) Cooling Mode Heating Mode Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F Minimum indoor temperature 16.0 / 60.8 11.0 / 51.8 Minimum indoor temperature...
INDICATOR LIGHTS Remote Control When there is infrared remote control operating signal, the signal receiver on indoor unit will made a <beep> for signal acceptance confirmation. Error Description Cool LED Error Indication Room sensor error 1 blink Pipe water sensor error 2 blinks Water pump error 6 blinks...
Page 9
AUSLEGUNG UND ADMESSUNG Innen-Gerät: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 SIEHE AUSSCHNITT A AUSSCHNITT A WASSERAUSTRITTSÖFFNUNG WASSEREINTRITTSÖFFNUNG Alle abmessungen sind in mm. VORSICHTMASSNAHMEN ! ACHTUNG ! VORSICHT • Die Installation und Wartung muß durch qualifizietes Personal Vor der Installation sind folgende wichtige Punkte zu prüfen.
INSTALLATION DES INNENGERÄTES 1. Vorbereitende Massnahmen Min. 0,5 m Min. 0,5 m Min. 0,5 m Wandelement Fußboden • Stromversorgung und Installation hat in Übereinstimmung mit den landesspezifischen Vorschriften zu erfolgen. • Netzspannungsschwankungen dürfen nicht um mehr als ±10% von der Nennspannung abweichen. Die Stromleitungen dürfen nicht zusammen mit Schweißtransformatoren auf einem Stromkreis liegen, da diese hohe Spannungsschwankungen verursachen können.
Page 11
5. Ablauftest • Verbinden Sie das Hauptablaufrohr mit dem flexiblen Ablaufschlauch. Speisewasser • Füllen Sie Wasser in den flexiblen Ablaufschlauch und überprüfen Sie die Rohrleitungen auf Undichtigkeiten. Hauptrohrleitung • Verbinden Sie nach Durchführung des Ablauftests den flexiblen Ablaufschlauch mit dem Ablaufanschluß amRaumgerät. Hinweis: Dieses raumgerät hat eine ablasspumpe für das abpumpen von Flexibler Ablaufschlauch kondenswasser.
Page 12
KABELANSCHLUSS Im folgenden wird der empfohlene Verdrahtungsplan gezeigt. Dieser kann je nach Kühlgerät abweichen und muss den örtlichen und nationalen Normen und Regelungen entsprechen. Modell: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2 FCU 3...
Page 13
BETRIEBSBEREICH Grenzwerte für den Betrieb: Wärmeträger : Wasser Wassertemperatur : 5 ~50°C Maximaler Wasserdruck : 16 bar Lufttemperatur : (siehe hier unten) Kühlender Modus Heizung Modus Temperatur Ts °C/°F Th °C/°F Temperatur Ts °C/°F Th °C/°F Mindest-Innentemperatur 16,0 / 60,8 11,0 / 51,8 Mindest-Innentemperatur 16,0 / 60,8...
Page 14
BETRIEBSLEUCHTANZEIGE Infrarot-Signalempfänger Wenn von der Infrarot-Fernbedienung ein Signal an das Gerät gesendet wird, bestätigt das Innengerät den Empfang mit einem Signalton. Fehlerbeschreibung Andere LED’s (kühl) Fehleranzeige Zimmersensor-Fehler 1 blinken Wasserleitungssensor-Fehler 2 blinken Wasserpumpen-Fehler 6 blinken Wasserleitungstemp-Fehler 5 blinken *Fensteröffnung aktiviert 3 blinken *Frostschutz-Modus aktiviert 7 blinken...
CONTOUR ET DIMENSIONS Unité Intérieure: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 VOIR DÉTAIL A DÉTAIL A PRISE DE SORTIE D’EAU PRISE D’ENTRÉE D’EAU Toutes les dimensions sont données en mm. PRÉCAUTIONS DE SÉCURITÉ ! ATTENTION ! AVERTISSEMENT •...
INSTALLATION DE L’UNITÉ INTÉRIEURE 1. Etude Preliminaire Du Site Min. 0,5 m Min. 0,5 m Min. 0,5 m Obstacle • L’alimentation électrique et l’installation doivent être conformes à la réglementation locale (p.ex. agréé EDF). • Les fluctuations de tension du réseau doivent rester dans la limite de ±10% de la tension nominale. Le climatiseur ne doit pas partager les lignes d’alimentation électrique avec des transformateurs de soudage, qui risquent de causer d’importantes fluctuations.
Page 17
5. Test D’évacuation • Connectez le tuyau d’évacuation principal au tuyau d’évacuation flexible. Envoyez • Envoyez de l’eau dans le tuyau d’évacuation flexible et vérifiez qu’il n’y a Tuyau l’eau pas de fuite dans la tuyauterie. d’évacuation • Lorsque le test est terminé, connectez le tuyau flexible au connecteur principal d’évacuation sur l’unité...
Voici une suggestion de raccordement électrique. Le câblage peut varier selon l’unité de refroidissement et doit se conformer au code et aux règlements locaux et nationaux. Modèle: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2...
L’INDICATEUR S’ALLUME Télécommande Lorsque la télécommande infrarouge émet un signal de fonctionnement, le récepteur de signal de l'unité intérieure émet un <bip> pour confirmer l'acceptation du signal. Description de l’erreur LED Froid Indication de l’erreur Erreur du capteur intérieur 1 clignotement Erreur du capteur de tuyauterie 2 clignotements Erreur de pompe à...
Page 21
OMTREK EN AFMETINGEN Binnenapparaat: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 ZIE DETAIL A DETAIL A WATERUITLAAT WATERINLAAT Alle afmetingen zijn in mm. VEILIGHEIDSMAATREGELEN ! ATTENTIE ! WAARSCHUWING • Installatie en onderhoud moeten uitgevoerd worden door Neem notitie van de volgende belangrijke punten bij installatie.
Page 22
INSTALLATIE VAN HET BINNENMODULE 1. Vooroverzicht locatie Min. 0,5 m Min. 0,5 m Min. 0,5 m Obstakel Vloer • Stroomvoorziening en installatie moeten voldoen aan wetten en voorschriften van plaatselijke autoriteiten (bv. energiebedrijf). • Fluctuaties in de spanning mogen niet hoger zijn dan ±10% van de nominale spanning. De stroomvoorziening moet onaf- hankelijk zijn van de stroomvoorziening voor lastransformatoren, die hoge fluctuaties in de voorziening kunnen veroorzaken.
Page 23
5. Afvoertest • Sluit op de hoofdafvoerbuisde flexiebele afvoerslang aan. Watertoevoer • Vul via de flexibele slang water, om op leidinglekkages te controleren. • Wanneer de test afgesloten is, kunt u de flexibele afvoerslang Hoofdafvoerbuis aansluiten op de afvoeraansluiting van het binnenmodule. Opmerking: Dit binnenmodule benut een afvoerpomp voor de afwatering van condenswater.
Page 24
AANSLUITING ELEKTRISCHE BEDRADING Dit is het bedradingsontwerp. Het kan veranderen, navenant het koelapparaat en moet voldoen aan de plaatselijkeen nationale wetten en voorschrifen. Model: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2 FCU 3 VALVE...
Page 25
WERKINGSBEREIK Bedrijfslimieten: Warmtedrager : Water Watertemperatuur : 5 ~50°C Maximale waterdruk : 16 bar Luchttemperatuur : (zie hieronder) Koelapparaat Modus Verwarming Modus Temperatuur Ts °C/°F Th °C/°F Temperatuur Ts °C/°F Th °C/°F Minimale binnentemperatuur 16,0 / 60,8 11,0 / 51,8 Minimale binnentemperatuur 16,0 / 60,8 Maximale binnentemperatuur...
INDICATORLAMPJES Afstandsbediening Zodra het infrarode bedrijfssignaal voor de aftandsbediening werkt, geeft de signaalontvanger van het binnenmodule een <pieptoon> af, ter bevestiging dat de signalen ontvangen worden. Storingsbeschrijving LED koeling Storingsindicatie Storing sensor kamer 1 x knipperen Storing sensor leidingwater 2 x knipperen Storing waterpomp 6 x knipperen Storing temperatuur leidingwater...
ESQUEMA Y DIMENSIONES Unidad Interior: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 MIRAR DETALLE A DETALLE A SALIDA DE AGUA ENTRADA DE AGUA Todas las dimensiones están en mm. PRECAUCIONES DE SEGURIDAD ! ADVERTENCIA ! CUIDADO • La instalación y el mantenimiento deben ser realizador por Asegúrese de seguir durante la instalación los siguientes puntos...
INSTALACIÓN DE LA UNIDAD INTERIOR 1. Recono Cimiento Preliminar Del Emplazamiento Min. 0,5 m Min. 0,5 m Min. 0,5 m Obstaculo Suelo • El suministro y instalación eléctricos deben ajustarse a los códigos y reglamentos de la autoridad local o nacional competente. •...
Page 29
5. Prueba de Drenaje • Conecte la tubería de drenaje principal a la manguera de drenaje flexible. Alimentación • Realice la alimentación de agua que procede de la manguera de drenaje de Agua Tubería de flexible y revise que no existan pérdidas en las tuberías. Drenaje Principal •...
Se muestra a continuación una propuesta de conexión. Puede cambiarse dependiendo de la unidad de refrigeración y debe cumplir con los códigos y regulaciones locales y nacionales. Modelo: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2...
CONDICIONES DE FUNCIONAMIENTO Límites de Funcionamiento: Transportador de agua: Agua Temperatura del agua : 5 ~50°C Presión máxima del agua : 16 bar Temperatura del aire: (como abajo) De Enfriamiento Mode Modo de calefacción Temperatura Ts °C/°F Th °C/°F Temperatura Ts °C/°F Th °C/°F Temperatura interior mín.
LUZ INDICADORA Control Remoto Cuando exista una señal de infrarojos de funcionamiento del control remoto, el receptor de señales de la unidad interior producirá un <beep> como confirmación de aceptación de señal. Descripción del Error Indicador Luminoso de Refrigeración Indicación de Error Error del sensor de espacio 1 parpadeo Error del sensor del tubo de agua...
DISEGNI E DIMENSIONI Unità Interna: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 VEDI DETTAGLIO A DETTAGLIO A USCITA ACQUA INGRESSO ACQUA Tutte le dimensioni sono in mm. NORME DI SICUREZZA ! CAUTELA ! AVVERTENZA Durante l’installazione, verificare accuratamente i punti seguenti.
INSTALLAZIONE DELL’UNITÀ INTERNA 1. Verifiche Preliminari Min. 0,5 m Min. 0,5 m Min. 0,5 m Osracolo Pavimento • L’impianto e gli allacciamenti elettrici devono rispondere alle norme e i regolamenti vigenti (ENEL). • Le fluttazioni del voltaggio di alimentazione non devono scostarsi dal voltaggio nominale di più del ±10%. Sulle linee elettriche di alimentazione non devono essere inseriti eventuali trasformatori da saldatura che per natura tendono a provocare delle alte fluttuazioni nel voltaggio.
Page 35
5. Test di Scarico • Collegare il tubo principale di scarico al relativo tubo flessibile. Alimentazione • Inserire acqua dal tubo flessibile di scarico e controllare la presenza Acqua di eventuali perdite dalla tubatura. Tubo Scarico Principale • Al completamento del test, collegare il tubo flessibile di scarico al relativo connettore sull’unità...
Questa è soltanto una proposta di collegamento dei cavi, che potrà essere diversa in funzione dell’unità e deve in ogni caso essere conforme agli standard e le norme locali e nazionali. Modello: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1...
RANGE DI FUNZIONAMENTO Limiti di utilizzo: Portante termico : Acqua Temperatura dell’acqua : 5 ~50°C Pressione massima dell’acqua : 16 bar Temperatura dell’aria : (vedi sotto) Modo Raffreddamento Modo Riscaldamento Temperatura Ts °C/°F Th °C/°F Temperatura Ts °C/°F Th °C/°F Temp.
SPIE DI CONTROLLO Telecomando Se è presente il segnale di funzionamento del telecomando a infrarossi, il ricevitore del segnale dell'unità interna emetterà un <bip> ad indicare la conferma di accettazione. Descrizione Errore Indicatore LED Cool Indicazione Errore Errore sensore ambiente 1 lampeggia Errore sensore acqua conduttura 2 lampeggio...
ΠΕΡΙΓΡΑΜΜΑ ΚΑΙ ΔΙΑΣΤΑΣΕΙΣ Εσωτερική μονάδα: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 ΒΛ. ΛΕΠΤΟΜΕΡΕΙΑ Α ΛΕΠΤΟΜΕΡΕΙΑ Α EΞOΛOΣ NEPOY EΙΣOΛOΣ NEPOY λες οι διαστάσεις είναι σε mm. ΠΡΟΦΥΛΑΞΕΙΣ ΑΣΦΑΛΕΙΑΣ ! ΠΡΟΣΕΞΤΕ ΙΔΙΑΙΤΕΡΑ ΤΑ ΕΞΗΣ ! ΠΡΟΣΟΧΗ • Η εγκατάσταση και η συντήρηση πρέπει να γίνονται απ...
Page 40
ΕΓΚΑΤΑΣΤΑΣΗ ΤΗΣ ΕΣΏΤΕΡΙΚΗΣ ΜΟΝΑΔΑΣ 1. Προκαταρκτική επισκ πηση της θέσης εγκατάστασης Min. 0,5 m Min. 0,5 m Min. 0,5 m Εμπ διο Πάτωμα • Η ηλεκτρική τροφοδοσία και η εγκατάσταση πρέπει να γίνονται σύμφωνα με τους κώδικες και τις ρυθμίσεις των τοπικών αρχών (π.χ. Εθνικ ς Φορέας...
Page 41
5. Έλεγχος αποχέτευσης • Συνδέστε τον κύριο αποχετευτικ σωλήνα στον εύκαμπτο αποχετευτικ σωλήνα. Τροφοδ τηση • Τροφοδοτείστε νερ απ τον εύκαμπτο αποχετευτικ σωλήνα για να ελέγξετε νερού Κύρια τη σωλήνωση για τυχ ν διαρροές. αποχετευτική • ταν συμπληρωθεί ο έλεγχος, συνδέστε τον εύκαμπτο αποχετευτικ σωλήνα αντλία...
Page 42
Πρ κειται για προτειν μενη σύνδεση καλωδιώσεων. Μπορεί να αλλάξει με βάση τη μονάδα ψύξης και πρέπει να είναι σύμφωνη με τον τοπικ και εθνικ κώδικα και τις τοπικές και εθνικές ρυθμίσεις. Μοντέλο: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1...
Page 43
ΕΥΡΟΣ ΛΕΙΤΟΥΡΓΙΑΣ ρια λειτουργίας: Θερμικ ς φορέας: Νερ Θερμοκρασία νερού: 5 ~ 65°C Μέγιστη πίεση νερού: 16 bar Θερμοκρασία αέρα: ( πως αναφέρεται κατωτέρω) Μονάδα ψύξης Μονάδα θερμικής αντλίας Θερμοκρασία Ts °C/°F Th °C/°F Θερμοκρασία Ts °C/°F Th °C/°F Ελάχιστη εσωτερική θερμοκρασία 16,0 / 60,8 11,0 / 51,8 Ελάχιστη...
Page 44
ΔΕΙΚΤΕΣ ΛΕΙΤΟΥΡΓΙΑΣ Τηλεχειριστήριο ¨ ταν υπάρχει λειτουργ σήμα τηλεχειριστηρίου υπερύθρων, ο δέκτης του σήματος πάνω στην εσωτερική μονάδα θα κάνει ένα <μπιπ> για επιβεβαίωση της αποδοχής του σήματος. Περιγραφή σφάλματος Απ κριση δείκτη LED Ένδειξη σφάλματος Σφάλμα αισθητήρα 1 αναλαμπή Σφάλμα...
ESBOÇO E DIMENSÕES Unidade Interior: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 VER DETALHE A DETALHE A SAÍDA DE ÁGUA ENTRADA DE ÁGUA Todas as dimensões estão em mm. PRECAUÇÕES DE SEGURANÇA ! CUIDADO ! AVISO Por favor tome nota dos seguintes pontos importantes ao instalar.
INSTALAÇÃO DA UNIDADE INTERIOR 1. Inspecção Preliminar Do Local Mín. 0,5 mt Mín. 0,5 mt Mín. 0,5 mt Obstáculo Chão • A instalação e corrente eléctrica estão em conformidade com os códigos e regulamentos da autoridade local (por exemplo, a Comissão Eléctrica Nacional/National Electrical Board).
Page 47
5. Teste da drenagem • Ligue o tubo de drenagem principal à mangueira flexível. Introduzir • Introduza água a partir da mangueira de drenagem flexível para Tubo de água verificar se existem fugas na tubagem. drenagem • No final do teste, ligue a mangueira de drenagem flexível ao conector principal de drenagem existente na unidade interior.
Esta é a ligação da cablagem proposta. Pode ser alterada tendo em conta a unidade refrigeradora e deve cumprir os códigos e regulamentos locais e nacionais. Modelo: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2...
Page 49
AMPLITUDE OPERACIONAL Limites operacionais: Portador térmico: Água Temperatura da água : 5 ~50°C Pressão máxima da água : 16 bar Temperatura do ar: (conforme indicado a seguir) Modo De Arrefecimento Modo De Aquecimento Temperatura Ts °C/°F Th °C/°F Temperatura Ts °C/°F Th °C/°F Temperatura interior mínima 16,0 / 60,8...
LUZES INDICADORAS Controlo remoto Quando existe um sinal operativo do controlo remoto por infravermelhos, o receptor do sinal da unidade interior irá emitir um sinal sonoro de confirmação <bip>. Descrição de erro LED fresco Indicação de erro Erro do sensor da divisão Pisca 1 vez Erro do sensor da água do cano Pisca 2 vezes...
СХЕМА И РAЗМЕРЫ Комнатный блок: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 СМОТРИ ДЕТАЛЬ А ДЕТАЛЬ А BOДOBЫПУСК BOДO3AБOP Все размеры указаны в мм. МЕРЫ ПРЕДОСТОРОЖНОСТИ ! ВHИMAHИE ! ОCTOPOЖHO Пожалуйста, обратите внимание на нижеследующие важные моменты • Установка и техническое обслуживание должны проводиться...
УСТАНОВКА КОМНАТНОГО БЛОКА 1. Предварительный Oсмотр Места Установки Мин. 0,5 м Мин. 0,5 м Мин. 0,5 м Препятствие Пол • Подвод электроснабжения и установка должны соответствовать положениям и правилам местной управляющей администрации (напр. Национальное управление по электричеству). • Колебание напряжения не должно быть более, чем ±10% от нормального напряжения. Провода электроснабжения должны...
Page 53
5. Проверка Cлива • Соедините главную дренажную трубу к гибкому Налейте дренажному шлангу. Bоду • Налейте воду из гибкого дренажного шланга для проверки Г лавная герметичности трубопроводов. Cливная Tруба • По завершении проверки, соедините гибкий дренажный шланг к дренажному штуцеру на внутреннем модуле. Примечание: Данный...
Page 54
ЭЛЕКТРИЧЕСКАЯ СХЕМА СОЕДИНЕНИЙ Данная схема электрических соединений является рекомендуемой. Она может изменяться в зависимости от применяемого водоохладителя и должна соответствовать требованиям местных и национальных правил и нормативов. МОДЕЛЬ: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 FCU 1 FCU 2...
РАБОЧИЙ ДИАПАЗОН Эксплуатационные ограничения: Тепловой носитель: Вода Температура воды : 5 ~50°C Максимальное давление воды: 16 бар Температура воздуха: (как указано ниже) Только охлаждение Обогревательный насос Температура Ts °C/°F Th °C/°F Температура Ts °C/°F Th °C/°F Мин. темп. в помещении 16,0 / 60,8 11,0 / 51,8 Мин.
Page 58
‹Ç ÜN‹TEN‹N MONTAJI ‹Ç ÜN‹TEN‹N MONTAJI ‹Ç ÜN‹TEN‹N MONTAJI ‹Ç ÜN‹TEN‹N MONTAJI ‹Ç ÜN‹TEN‹N MONTAJI 1. Montaj Yeri Ön ‹ncelemesi 1. Montaj Yeri Ön ‹ncelemesi 1. Montaj Yeri Ön ‹ncelemesi 1. Montaj Yeri Ön ‹ncelemesi 1. Montaj Yeri Ön ‹ncelemesi Min.
Page 59
5. Tahliye Testi 5. Tahliye Testi 5. Tahliye Testi 5. Tahliye Testi 5. Tahliye Testi • Ana tahliye borusunu elastik boruya ba¤lay›n. Besleme • Boru tesisat›n›n s›z›nt› yap›p yapmad›¤›n› kontrol etmek için Suyu elastik tahliye hortumundan su verin. Ana tahliye borusu •...
Page 60
Bu önerilen bir elektrik tesisat› ba¤lant›s›d›r. So¤utucu ünitesine ve uyulmas› gereken yerel ve ulusal yönetmeliklere ba¤l› olarak de¤iflebilir. Modeller: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 Modeller: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1 Modeller: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1...
Page 61
ÇALIfiMA ARALI⁄I ÇALIfiMA ARALI⁄I ÇALIfiMA ARALI⁄I ÇALIfiMA ARALI⁄I ÇALIfiMA ARALI⁄I Çal›flma S›n›rlar›: Çal›flma S›n›rlar›: Çal›flma S›n›rlar›: Çal›flma S›n›rlar›: Çal›flma S›n›rlar›: Termal Tafl›y›c› : Su Su S›cakl›¤› : 5 ~50°C Maksimum Su Bas›nc› : 16 bar Hava S›cakl›¤› : (afla¤›da gösterildi¤i gibi) So¤utma ünitesi So¤utma ünitesi So¤utma ünitesi...
Page 62
GÖSTERGE LAMBALARI GÖSTERGE LAMBALARI GÖSTERGE LAMBALARI GÖSTERGE LAMBALARI GÖSTERGE LAMBALARI Uzaktan Kumanda Uzaktan Kumanda Uzaktan Kumanda Uzaktan Kumanda Uzaktan Kumanda K›z›lötesi uzaktan kumanda çal›flma sinyali oldu¤u zaman, iç ünitedeki sinyal al›c›s›ndan sinyalin kabul edildi¤ini do¤rulamak bir <bip> sesi gelecektir. Hata Tarifi Hata Tarifi So¤uk LED So¤uk LED...
Page 66
Head office: Zandvoordestraat 300, B-8400 Oostende, Belgium Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan http://www.daikin.com/global/ Part No.: R08019029228...