Central Ventilation Units KWL EC.. D Pro/WW
2.2

Condensation outlet

The humidity of extract air condenses to water during the heating period. A lot of condensate can build up in new buil-
dings with large numbers of people. The condensate collected in the stainless-steel condensation tub is discharged
using a ball siphon (included in the scope of delivery). In this respect, there must be an incline of at least 3° and the
customer must ensure the connection to the local drainage system. An open outlet should be installed due to odour
development from a dried-out siphon.
The drainage pipe route must not rise above the siphon!
m
The condensation outlet must be made frost-proof!
2.3

Flange connection / connecting pieces

The KWL EC ... Pro / WW types are supplied with a flange connection as standard.
K
M8
C
Duct-to-pipe connecting pieces are available in the Helios range:
H
h
J
Fig.6
359
350
900
399
390
1200
489
480
1400
ø 10
y
Z
z
376
229
230
Unit type
610
375
375
KWL EC 700 D..
Fig.6
770
485
485
Fig.7
KWL EC 1400 D..
KWL EC 2000 D..
Fig.8
The piping must be firmly and tightly connected to the connection valves. Refer to the illustrations for the
+
arrangement of ventilation ducting.
+
m
The operation of the KWL unit in conjunction with an active cooling system, e.g. air conditioning system,
is not permissible!
2.4

Air ducting, Ventilation circuit

With regard to planning and design, use the shortest possible lines. Airtight connections and changeovers must be
ensured. To avoid pressure losses, dirt build-up and noise, use smooth ducts (plastic or rigid ducting). For main lines
(outside, outgoing air, supply air distributor, extract collector), DN (KWL EC 700 D = 250 mm; KWL EC 1400 D = 315
mm; KWL EC 2000 D = 400 mm) or corresponding ducting should be provided, and the ø is reduced accordingly for
branch lines.
Outside and outgoing air pipes are to be insulated in an appropriate way to reduce condensation. The minimum insu-
lating thicknesses pursuant to DIN EN 1946-6, 05/2009 are to be observed. If supply and extract air ductwork runs
through unheated rooms, insulation must be provided to reduce heat losses. Supply air should be supplied to primary
rooms and extraction should take place in secondary rooms. To balance the whole system, supply and extract air
openings should be provided with adjustable valves (accessories).
A filter (accessory) is to be connected for the extraction of polluted extract air. The installation of extractor hoods to the
system is not permitted (reasons: dirt, fire danger, hygiene). Sufficient overflow openings (door gap, door grilles) are to
be provided to ensure air circulation within the room.
Fig.3
Condensate
drain outlet,
Ø 22 mm
Fig.5
c
I
K
k
Fig.7
872
336
45
1312
416
45
1632
643
45
ø 10
E
F
m
Dim. in mm
349
697
465
Description
420
851
772
KWL-ÜS 700 D
495
1002
972
KWL-ÜS 1400 D
KWL-ÜS 2000 D
6
Incline min 3°
Unit type
Dim.
KWL EC 700 D
mm
KWL EC 1400 D
mm
KWL EC 2000 D
mm
c
Fig.8
300
500
600
ø 10
n
Dim. in mm
366
Ref. no.
Duct diameter in mm
499
4206
619
4207
4208
Fig.4
Condensate drain outlet
with ball siphon
C
c
D
d
324
300
224
200
524
500
274
250
624
600
324
300
Dim. in mm
250
315
400

Publicité