1. OPERATION.
SPEEDMATIC Easy is a compact automatic control device designed for the single-phase or three-phase pump´s (depending
on model) automation, with an electronic system managed by a software responding to the rigorous requirements of
efficiency and safety of the most important builders of pumps. It includes a frequency inverter that regulates the speed of the
pump in order to keep constant the pressure independently of the flow given.
The system incorporates a LCD screen where the parameters configuration is very easy and intuitive. Once the configuration
parameters are introduced, the SPEEDMATIC manages the start-up of the pump and the frequency inverter. It assures a
constant pressure and an important costs reduction because at any time the control will feed the system with the right and
necessary output, obtaining a maximum energetic efficiency. In order to establish the ideal pressure in the installation is
suitable to consider following criteria:
Hm:
Max. water column height in m. It depends on the number of floors and it corresponds to the height from the pump
to the last floor. Every 10 m of height corresponds approximately to 1 bar (0.98) bar.
Pw:
Available minimum pressure in last floor (usually 1.5 bar).
Pc:
Pressure drop. It can be considered with a simplified criteria as 0.033 bar/m.
Prmin: Minimum resultant pressure. It is the sum of the previous pressures and it will be the operating pressure of the pump.
Example for a 5 floors building (15 m) with pump placed at level 0:
Hm =15 m @ 1.5 bar Pw = 1,5 bar
2. CLASSIFICATION AND TYPE.
According to EN-60730-1 the SPEEDMATIC is a device of independent assembly, type 1B with software of class A. Control
circuit for alternating current motor with power factor cosφ ≥ 0,6. Pollution Degree 2. Rated impulse voltage: 2500V/CATII.
Class of disconnection 1Y (electronic disconnection).
3. MAIN CHARACTERISTICS.
DN inlet port G1 1/4 " male ISO 228.
n
DN outlet port G1 1/4 " male ISO 228.
n
Frequency inverter for the pump control.
n
Control and safety system against over-intensities.
n
Control and safety system against dry operation.
n
ART function (Automatic Reset Test). If the device has been stopped due to the action of the safety system against
n
over-intensities, the ART tries to connect the pump, with a programmed periodicity because the water supply could
have been restored
Automatic restore system after an interruption of power supply. System is activated in AUTOMATIC mode keeping the
n
configurationparameters (see "CONFIGURATION" chapter).
Inside pressure transducer.
n
Control panel (see chapter 7): 2 digits display, pushbuttons, led lights and digital gauge providing instantaneous
n
lecture of pressure.
AIS function (Anti-Ice System). If temperatures under 5 ºC are detected it will start periodically the pump avoiding the
n
freezing of the water inside the pump.For environment temperatures under 0ºC it is very important to take
measures to avoid water freezing.
Register of operational controls: infomation about operating hours, counter of starts, counter of connections to the power
n
supply.
Register of alarms: information about type and number of alarms since the starting up of the device.
n
Connections for detection of minimum water level in aspiration tank. This system is independent of the safety against dry
n
operation. Is optional.
4. TECHNICAL CHARACTERISTICS.
Type
n
Power supply voltage
n
Frequency
n
Max. current each phase
n
Max. peak of current
n
Max. operating pressure
n
n
Max. set pressure
n
Protection index
n
Max. water temperature
Max. environment temperature
n
Max. flow
n
* Easy 09 MM is provided with 10 A fuse.
* Easy 12 MM is provided with 16 A fuse.
* Easy 06 MT is provided with 16 A fuse.
* Easy 10 MT is provided with 20 A fuse.
Pc=15 x 0,033 bar @ 0,5 bar
EASY 09MM
EASY 12MM
~1x230 ± 20% V
~1x230 ± 20% V
50/60 Hz
50/60 Hz
9A (~1 230 V)
12A (~1 230 V)
20% during 10"
20% during 10"
15 bar
15 bar
0.5÷8 bar
0.5÷8 bar
IP55
IP55
40ºC
40ºC
0-50ºC
0-50ºC
10.000 l/h
10.000 l/h
-8-
Prmin = 1,5 + 1,5 + 0,5 = 3,5 bar
EASY 06MT
~1x230 ± 20% V
50/60 Hz
6A (~3 230 V)
20% during 10"
15 bar
0.5÷8 bar
IP55
40ºC
0-50ºC
10.000 l/h
english
Easy 10 MT
~1x230 ± 20% V
50/60 Hz
10A (~3 230 V)
20% during 10"
15 bar
0.5÷8 bar
Ip55
40ºC
0-50ºC
10.000 l/h

Publicité