Operating Conditions - WIKA A-10 Mode D'emploi

Masquer les pouces Voir aussi pour A-10:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Specifications
3.4 Accuracy
The model A-10 is optionally available with an improved non-linearity. Depending on the version the
following values apply.
GB
Non-linearity per BFSL (IEC 61298-2)
Non-repeatability
Long-term drift (per IEC 61298-2)
Signal noise
Settling time
Temperature error at 0 ... 80 °C
Measuring deviation of the zero signal
Accuracy at room temperature
1) Including non-linearity, hysteresis, zero offset and end value deviation (corresponds to measured error per IEC 61298-2). Calibrated in
vertical mounting position with process connection facing downwards.

3.6 Operating conditions

Ingress protection (per IEC 60529)
The ingress protection depends on the type of electrical connection (see table under 3.7 "Electrical
connections, specifications").
Vibration resistance
10 g (IEC 60068-2-27, under resonance)
20 g available on request
Shock resistance
500 g (IEC 60068-2-6, mechanical)
12
Standard
≤ ±0.5 % of span
≤ 0.1 % of span
≤ ±0.1% of span
≤ ±0.3% of span
< 4 ms
Typical: 1 % of span
Maximum: 2.5 % of span
Typical: ≤ ±0.5 % of span
Maximum: ≤ ±0.8 % der Spanne
≤ ±1 % of span
1)
WIKA operating instructions pressure transmitter model A-10
Option
≤ ±0.25 % of span
≤ 0.1 % of span
≤ ±0.1% of span
≤ ±0.3% of span
< 4 ms
Typical: 1 % of span
Maximum: 2.5 % of span
Typical: ≤ ±0.15 % of span
Maximum: ≤ ±0.4 % of span
≤ ± 0.5 % of span,
≤ ± 0.6 % of span (at 0 ... 5 V)

Publicité

Table des Matières
loading

Table des Matières