Hach sc1000 Profibus DP/V1 Manuel D'utilisation De Base page 10

Masquer les pouces Voir aussi pour sc1000 Profibus DP/V1:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 41
Figure 4 Profibus configuration menu—Telegram list with new tag
1
Headline
2
Data position in the configured
Profibus slave (in 2 byte words)
3
Tag name to identify the
configured data.
Description
Option
TELEGRAM
Manages the Telegram data structure.
The devices and the device data tags included in the Telegram
can be selected.
English
7
4
Data type
float=floating point value
int=integer numbers
sel=integer value resulting from
a enum (selection) list
5
Data status
r=data are read only
r/w=read/write
Description (continued)
Option
PROFIBUS DP Selects one of the following options:
Address— Changes the slave address
Data order— Sets the sequence of bytes when transmitting
floating point values. A floating point value consists of 4 bytes.
Normal = IEEE Float Big Endian (Default setting)—The
pairs are not swapped. This mode fits to all known Profibus
master systems.
Swapped = IEEE Float word wise swapped: Swaps the first
pair of bytes with the last pair.
SIMULATION
Simulation— Simulates two floating point values and error/status
to substitute a real instrument. Select the following options and
use the arrows to enter the values or use the default setting:
Simulation: Turns the simulation on or off.
Yes: Starts a simulation
No: Stops a simulation (Default setting)
Period: Sets the time the first floating point value needs to
run through the whole range between MINIMUM and
MAXIMUM—2 min (Default setting)
Maximum: Sets the upper limit for the first floating point
value.—20.0 (Default setting)
Minimum: Sets the lower limit for the first floating point
value —10.0 (Default setting)
Error: The value entered in this menu will be set in the first
simulated tag—16 (Default setting)
Status: The value entered in this menu will be set in the
second simulated tag—5 (Default setting)
Toggle: Changes the direction of the simulated ramp.
Test/maint:
Enabled: Sets the TEST/MAINT bit (0x0004) of every status
register of every configured slave in the cyclic Profibus
telegram to indicate the "Service" mode.
Disabled: Normal operation mode (Default setting)
VERSION
Software version of the Profibus network card.
LOCATION
Edits the location name.

Publicité

Table des Matières
loading

Table des Matières