4.7 EMISSIONS

Class Limit 3 = 80 mg/kWh
The burners' emission values (according to
EN 676) prove much lower than the limits laid
down by the strictest standards. The flame's di-
stribution and its spread over a large surface
means that the burner manages to limit the for-
mation of thermal NOx, the main causes of pol-
lutant emission.
min.
max.
Modulation
Modulation
D9715
25 kW
120 kW

4.8 IONISATION CURRENT

The minimum current necessary for the
control box operation is 5 μA. The burner gi-
Connector
ves a much higher current, meaning that
Control-box
checking is not usually required. Should
you want to measure the ionization current
anyway, you must open the connector
Probe
(CN1) (see wiring diagram page 6) inserted
D5006
in the red wire and insert a microammeter.
3328
13