3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1 HEAT GENERATOR PLATE
Make holes in the plate shutting off the combustion chamber as illu-
strated in fig. 2. The position of the threaded holes may be marked
using the gasket joint supplied with the burner.
3.2 BOILER FIXING,
To install, proceed as follows:
Fasten the burner (1) to the boiler's door (2) by means of the four
screws and (where necessary) the nuts supplied, placing the insula-
ting gasket (3) between the two.
3.3 PROBE AND ELECTRODE POSITIONING,
WARNING
Before installing the burner on the boiler, make sure the probe and electrode are positioned correctly as in Fig. 4.
Do not turn the electrode: position it as illustrated. Placing the electrode near the ionization probe may result in the
control box amplifier being damaged.
Fig. 4
D7507
3328
(see fig. 3)
2
1 7 5
Electrode
Probe
3
D9767
(see fig. 4)
4
GB
Fig. 2
1 5 0
Fig. 3
1
4 . 5 - 5 . 5
D7505