diagrams provided with the hydronic indoor
unit.
NOTE:
It is also suggested to verify that the
characteristics of the mains power supply are
adequate for the power consumption indi-
cated in the table of electrical data.
IMPORTANT: Before carrying out any opera-
tion on electrical parts, make sure the power
supply is disconnected. Check that the mains
supply voltage corresponds to the nominal
10.7 MAINTENANCE
IMPORTANT:
Maintenance operations must
be carried out only by a service centre au-
thorised by the manufacturer or by qualified
personnel. For safety reasons, before per-
forming any maintenance or cleaning opera-
tions, switch off the unit.
Cleaning
If it is necessary to clean the control panel (user
10.8 TROUBLESHOOTING
If the unit to which the EVO controller is con-
nected is not working properly, before request-
ing service, perform the checks indicated in the
table in the unit's installation, use, and mainte-
nance manual. If the problem cannot be solved,
PROBLEM
The control panel does not turn on
The control panel displays a probe alarm
Incorrect reading of water temperature
Incorrect reading of air temperature on the control panel
Absence of communication with the monitoring system
Absence of communication with the MASTER in a SMALL network on
RS485
data of the hydronic indoor unit (voltage,
number of phases, frequency) shown on the
rating plate on the unit. The supply voltage
may not undergo fluctuations exceeding
±5% of the rated voltage. The electrical con-
nections must be made in accordance with
the wiring diagram provided with the spe-
cific hydronic indoor unit and the regulations
in force.
interface):
Ū use a soft cloth;
Ū never pour liquids onto the unit, as this could
cause electrical discharges and damage the
internal components;
Ū never use harsh chemical solvents;
Ū do not introduce metal parts through the
grille of the user interface's plastic casing.
contact the dealer or service centre.
INFO:
For further information on mainte-
nance, cleaning, and troubleshooting, refer
to the manual of the unit on which the con-
troller is installed.
SOLUTION
Check the correct connection to the on-board circuit board (wiring and
polarity)
Check the power supply of the circuit board (STATUS LED on)
Replace the connection cable to the circuit board
Check that the circuit board is wired correctly
Verify the correct positioning of the probe inside the traps
Check that the airflow through the control panel is not blocked
Check that the control panel is not affected by external heat sources
Adjust the air probe offset parameter to calibrate the probe
Check that the RS485 line is wired correctly
Check the correct parameter configuration of the SLAVE controller
Check the correct setting of the communication parameters on the mon-
itoring system
Check that the PLC line is wired correctly
Check the correct parameter configuration of all network controllers
53