Ū Hydronic indoor unit ON/OFF status
Ū Alarm presence
Ū Dehumidification call
Ū Humidification call
Ū High room temperature
Ū Low room temperature
Ū Lack of heating water enabling signal
Ū Lack of cooling water enabling signal
Ū From the monitoring software and selecta-
ble by means of the configuration parameter
"Configuration O7". Moreover it is possible to
choose, with the setting of the next param-
eter "Digital output logic", whether the relay
status should follow the NO (Normally Open)
or NC (Normally Closed) logic.
5.2 REGULATION PARAMETERS LIST
ID
Description
R1
Minimum limit cooling SET
R2
Maximum limit cooling SET
R3
Minimum limit heating SET
R4
Maximum limit heating SET
R5
Minimum limit humidity SET
R6
Maximum limit humidity SET
R7
Hysteresis humidity
R8
Offset on humidity reading
R9
Modulating fan minimum value
R10 Modulating fan maximum value - Cooling 100%
R11 Modulating fan maximum value - Heating 100%
R12 Air probe offset
R13 Water probe offset
R14 Water probe offset, heating
R15 Air stratification offset
R16 Hysteresis Economy
R17 Cooling water enabling signal SET-POINT 17.0°C
R18 Cooling water enabling signal hysteresis 5.0°C
R19 Heating water enabling signal SET-POINT 37.0°C
R20 Heating water enabling signal hysteresis 7.0°C
R21 Dehumidification water enabling signal
SET-POINT
R22 Dehumidification water enabling signal
hysteresis
R23 Valve water enabling signal SET-POINT
R24 Valve water enabling signal hysteresis
R25 Heating element water enabling signal
SET-POINT
R26 Heating element water enabling signal
hysteresis
5.1.3 Stand-by mode
After 30 seconds during which no operation is
performed on the user interface keypad, the
main screen goes into standby mode, and dis-
plays the room temperature. Touch the screen at
any point to return to the HOME screen.
5.1.4 Interruption in the serial
If the serial connection is interrupted with the
controller set as SLAVE, EVO-2-TOUCH will main-
tain the ON/OFF and SUMMER/WINTER mode
settings from the monitoring software or restore
the last settings from the keypad depending on
the selection of the corresponding configura-
tion parameter.
Default
ID
Description
10.0°C
R27 Minimum temperature control SET-POINT 9.0°C
35.0°C
R28 Minimum temperature control hysteresis 1.0°C
5.0°C
R29 Neutral zone
30.0°C
R30 % modulating fan in standby
35%
R31 JONIX - operating mode
75%
R32 JONIX - duration of manual cycles
5%
R33 JONIX - post ventilation duration
0%
20%
0.0°C
0.0°C
0.0°C
0.0°C
0.0°C
10.0°C
2.0°C
30°C
5.0°C
39.0°C
2.0°C
connection
Default
5.0°C
20%
VENTILATION
+POST
5 min.
2 min.
37
FC66005977