Code
Text display
E04.10
5 Unsuccessful burners starts detected
E04.11
VPS Gas Valve proving failed
E04.12
False flame detected before burner start
E04.13
Fan speed has exceeded normal operating
range
E04.14
The burner temperature and burner setpoint
differ more than a parameter defined by the
GVC for more
E04.15
The flue gas pipe is blocked
E04.17
The driver for the gas valve is broken
E04.18
The flow temperature is less than the
minimum defined by the GVC parameter
E04.19
Mass Flow Sensor Communciation
E04.20
MassFlowSensor Deviation
E04.21
Deviation in burner sensor 1 and burner
sensor 2 detected
E04.23
Gas Valve Control internal locking
E04.24
No gas family found during gas family
detection mode
7666743 - v.01 - 05092016
Description
Five failed burner starts:
No ignition spark:
Check the wiring between the PCU electronic PCB and
the ignition transformer.
Check that the SU electronic PCB is correctly in place.
Check the ionisation/ignition electrode.
Check breakdown to earth.
Check the condition of the burner set.
Check the earthing.
SU electronic PCB faulty: replace the electronic PCB.
Ignition spark but no flame:
Vent the gas pipes to remove air.
Check that the air inlet and flue gas discharge flues are
not blocked.
Check whether the gas tap is properly open.
Check the gas supply pressure.
Check the operation and setting of the gas valve unit.
Check the wiring on the gas valve unit.
SU electronic PCB faulty: replace the electronic PCB.
Presence of the flame but insufficient ionization (<4 µA):
Check whether the gas tap is properly open.
Check the gas supply pressure.
Check the ionisation/ignition electrode.
Check the earthing.
Check the wiring on the ionization/ignition electrode.
Gas leakage control fault:
Bad connection: check the wiring and connectors.
VPS gas leakage control defective: replace the GPS.
Gas valve unit faulty: replace the gas valve unit.
False flame signal:
The burner remains very hot: Set the O
Ionisation current measured but no flame should be pre­
sent: check the ionisation/ignition electrode.
Faulty gas valve: replace the gas valve.
Faulty ignition transformer: replace the ignition transformer.
Fan fault:
Bad connection: check the wiring and connectors.
Fan operates when it should not be operating: check for ex­
cessive chimney draught.
Faulty fan: replace the fan.
-
-
Gas valve fault:
Bad connection: check the wiring and connectors.
Faulty gas valve: replace the gas valve.
-
-
-
-
-
-