11 En cas de dérangement
Code
Text display
E02.04
Erreur de paramètre
E02.13
Entrée blocage de l'unité de commande
provenant de l'environnement externe de
l'appareil
E02.15
External CSU Timeout
E02.17
Expiration du temps de retour de
communication avec l'unité de commande des
vannes de gaz
E02.35
Dispositif critique de sécurité déconnecté
E02.47
Failed Connecting Function Groups
E02.48
Function Group Configuration Fault
E02.51
Parameter error from the Gvc
E02.52
Gvc Burner Profile Error
E04.00
Safety parameters Level 5 are not correct or
missing
E04.01
Flow temperature sensor is either shorted or
measuring a temperature above range
E04.02
Flow temperature sensor is either removed or
measuring a temperature below range
E04.03
Measured flow temperature above savety limit -
E04.04
Flue temperature sensor is either shorted or
measuring a temperature above range
E04.05
Flue temperature sensor is either removed or
measuring a temperature below range
E04.06
Measured flue temperature above limit
E04.07
Deviation in flow sensor 1 and flow sensor 2
detected
E04.08
Safety input is open
E04.09
Deviation in flue sensor 1 and flue sensor 2
detected
70
Description
Configuration error or factory settings incorrect:
Parameters are not correct:
Restart boiler
Reset
and
Replace the control panel if it is defective.
Blocking input is active:
External cause: remove external cause.
Wrong parameter set: check the parameters.
CSU time out:
Bad connection: check the wiring and connectors.
Faulty CSU: replace CSU.
Communication error with the safety PCB:
Bad connection: check the wiring and connectors.
Control unit failure: replace the control unit.
-
-
-
-
-
Safety parameters not OK:
Bad connection: check the wiring and connectors.
Flow temperature sensor short circuited:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has been
correctly fitted.
Faulty sensor: replace the sensor.
Flow temperature sensor open:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has been
correctly fitted.
Faulty sensor: replace the sensor.
-
-
-
Flow temperature sensor deviation:
Bad connection: check the connection.
Faulty sensor: replace the sensor.
Air pressure differential switch activated:
Bad connection: check the wiring and connectors.
Pressure in flue gas duct is or was too high:
Non-return valve does not open.
Siphon blocked or empty.
Check that the air inlet and flue gas discharge flues are
not blocked.
Check the cleanliness of the heat exchanger.
-
.
7666743 - v.01 - 05092016