5. Commissioning, operation
Requirements for mounting point
The mounting point must meet the following conditions:
Sealing faces are clean and undamaged.
Sufficient space for a safe electrical installation.
For information on tapped holes and welding sockets, see Technical information IN 00.14 at www.wika.com.
Permissible ambient and medium temperatures remain within the performance limits. Consider possible restrictions
on the ambient temperature range caused by mating connector used.
→ For performance limits see chapter 9 "Specifications"
Sealing variants
Parallel threads
Seal the sealing face  with flat gasket, lens-type
sealing ring or WIKA profile sealing.
Tapered threads
Wrap threads with sealing material
(e.g. PTFE tape).
Mounting the instrument
The max. torque depends on the mounting point (e.g. material and shape). If you have any questions,
please contact our application consultant.
→ For contact details see chapter 1 "General information" or the back page of the operating instructions.
1. Seal the sealing face (→ see "Sealing variants").
2
At the mounting point, screw the pressure transmitter in hand-tight.
.
3
Tighten with a torque spanner using the spanner flats.
.
WIKA operating instructions pressure transmitter, model A-10
per EN 837
per ISO 1179-2 (formerly
NPT, R and PT
DIN 3852-E)
EN
9