Main Board - mundoclima MUCSR-12-H11 Manuel D'installation Et L'utilisauter

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 86
Wiring diagram of indoor unit:
WIRE CONTROLLER
(Includes IR receiver)
WIFI MODULE
WF105 (CL09002)
(Optional)
Wiring diagram of Twin system (2x1):
MASTER
INDOOR UNIT
X Y E
Use shielded cable for interconnection (3x0,75mm2)
Outdoor unit power supply
230V or 400V (according your model)
50 Hz
Operation of external signals:

MAIN BOARD

JR6
FRESH AIR ALARM
ON/OFF
CN8
CN33
CN23
Fresh air
Connection to the panel
signal
DISPLAY
FRESH AIR
CN43
MAIN BOARD
See Note 1
4
4
Models 12 and 18: CN40
Models 24 to 60: CN38
4
4
Copy/
Swing
Timer
Day off/Del
Confirm
Back/Turbo
Follow me
Mode
-
+
Fan speed
(Lock)
WIRE CONTROLLER
KJR-120G2 (CL09210)
SLAVE
INDOOR UNIT
X Y E
- ON/OFF signal:
To use the signal ON / OFF you should cut away the jumper JR6 in indoor unit main PCB.
The operation is as follows:
1) With the unit running if the contact CN23 opens unit stops and remote control is locked,
CP shown in the display.
2) With the unit stoped if the contact CN23 opens unit will continue stop and remote control
is locked, CP shown in the display.
NOTE: Only CP shown in the display if the unit has a digital display.
The wired remote control KJR-120 also shows the CP code.
- ALARM signal:
The alarm signal close the port when the unit indicates an error code.
- FRESH AIR signal:
The 'Fresh Air' signal provides a 230Vac output (max. 200W or 1A load) when the machine
is in operation, this signal can be used to activate an auxiliary fan supplying fresh air.
Remote
Alarm
signal
ON/OFF
Note 1: If connect the Wire controller KJR-120G2 at the same
time than the WIFI module, the wire controller KJR-120G2,
must be connected to the Wifi module, please check
the detailed information in the wired controller or WIFI
module manual.
Connection to the panel
ALARM
ON/OFF
CN23
CN33
CN3
L
N
S
Outdoor unit
interconnection
Note: Twin system and Central controller use same terminal X Y E,
so these two functions you can just choose one .
Indoor unit setting:
SW8
"MAIN NO SLAVE" means the unit is set as an indoor unit of 1 drive 1 system;
"MAIN" means the unit is set as a master indoor unit of a twin system;
"SLAVE" means the unit is set as a slave unit of a twin system.
62
The terminals that are between dashed
lines is optional its use

Publicité

Chapitres

Table des Matières
loading

Table des Matières