Mounting; Pipework - Würth LATENTO 500 Notice De Montage

Masquer les pouces Voir aussi pour LATENTO 500:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.2 Mounting

Heed the following points when selecting the installation site for the LATENTO XW:
Frost-protected room.
Level, clean swept floor.
Do not subject the LATENTO to direct solar radiation
(the UV can destroy the plastic).
Heed the load-bearing capacity of the foundation, the filled LATENTO 500
weighs approx. 650 kg.
Keeping heat-losses as little as can be, place the LATENTO in the vicinity of the
reheating heat generator.
If possible, mount system in a heated room to minimize heat-losses
(ENEV – Energy Saving Decree).
Note

6.3 Pipework

Caution
A thermal mixing valve (Item no. 878 700 021) must be installed to the hot water
outlet of the domestic water heat exchanger so as to prevent scalds. The hot water
heat exchanger should be 60 °C according to DIN EN 806-2 (June 2005).
26
For operation with electrical heating element (878 700 039):
The screwing of the electrical heating element into the LATENTO
storage tank should take place before its filling and piping.
In areas with low room height it can be necessary to tilt the
LATENTO storage tank in order to insert the electrical heating
element.
Heed the regulations of the local water distribution company
and relevant DIN standards when connecting. The connections
must be made pressure-tight. The component-tested safety instal-
lations have to be installed according to DIN 4753, Part 1,
para. 6.3-7 (safety valve, reflux valve, pressure reducing valve,
drainage, control and safety device).

Publicité

Table des Matières
loading

Table des Matières