The storage tank has identical temperatures on top and bottom
Are the submersible sensors fitted at the right height?
Has a too strong circulating pump been installed?
Is the running time of the circulating pump too long?
Does hot water enter the cold water supply?
Pressure drop in the system
Pressure drop in the first weeks through escaping dissolved
air is normal!
Pressure fluctuations of up to 0.3 bar are normal during operation!
Check system for leak tightness.
Check safety valve for correct installation, leak tightness and
function.
Was the bleeding valve shut again after filling?
Has the expansion vessel been regulated correctly or is it broken?
Storage tank cools down over night without hot water consumption
Does the hot water loading pump run at night? Check the
controller settings!
Are all connections insulated?
Has the hot water outlet been directly laid upwards? (Microcircula-
tion!) Make the connection to the side or use siphon design!
Does the solar circuit pump run at night? Change timer setting!
Are the gravity brakes functional? Possibly clean them?
Is the gravity circulation in the circulation line too strong? Employ a
stronger reflux valve or integrate an electric 2-way valve after the
circulating pump!