Toshiba RBC-TWP101E Manuel D'installation page 5

Branch kit 1:5
Masquer les pouces Voir aussi pour RBC-TWP101E:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Branch Kit 1:2
<RAV-SM2246AT8, SM2806AT8 series>
Outdoor unit
Pipe Length
(One Direction)
Outdoor Unit -
Height
Difference
*
Ensure that the shortest pipe length complies with the following:
L + b ≥ 5 m
a ≥ b
CAUTION
When planning a layout for Units A and B, comply with the following:
1. The lengths after branching ("a" and "b") should be equal if feasible. Install Units A and B
so that the difference of the branching lengths becomes less than 10 m if the lengths
cannot be equal due to the branch pipe position.
2. Install Units A and B on the same level. If Units A and B cannot be installed on the same
level, the difference in level should be limited to 0.5 m or less.
3. Be certain to install Units A and B in the same room. Units A and B cannot be operated
independently each other.
Indoor unit B
Full length (L + a or L + b)
Branch piping (a, b)
Difference of branch piping length
(b – a, or a – b)
Outdoor Unit Installed
Above Indoor Unit
Indoor Unit
Outdoor Unit Installed
(H)
Below Indoor Unit
Between Indoor Units (Δh)
Remarks : Total equivalent length 125 m or less
Indoor unit A
b
a
Branch
Branch
piping
piping
L
Main piping
4
H
Below 100 m
(actual length)
Below 20 m
(actual length)
Below 10 m
Below 30 m
Below 30 m
Below 0.5 m
EN
EN