Technical description
Turns
Fig. 4:
Flow chart
Set the flow rate as follows:
Carry out setting whilst the circulation
pump is in operation.
1.
Close the valve spindle with a 5 mm
hexagonal spanner.
2.
Open the valve spindle (see Fig. 3 on page
20 (4)) by turning it anticlockwise
according to the calculated preset value.
140655281-V01.07.2021
All manuals and user guides at all-guides.com
Flow rate qm [kg/h]