WUV040T2AA-N
ESP: 0.10"WC - 0.50"WC
Cool Jumper
A/C Ton
CFM
A (MAX)
2.5T
554
B
2.0T
479
C
1.5T
342
D
N/A
WUV040T2AA-N
ESP: 0.10"WC - 0.50"WC
Cool Jumper
A/C Ton
CFM
A (MAX)
2.5T
751
B
2.0T
651
C
1.5T
495
D
N/A
NOTE
Airfl ow based on approximately 375-400 CFM/Ton. Refer to Figure 34 in the manual.
FIGURE 33 - INTEGRATED FURNACE IGNITION CONTROL
PARK
TERMINALS
ELECTRONIC
AIR CLEANER
POWER
HUMIDIFIER
120 VAC
MOLEX
120 VAC NEUTRAL
HEAT STAGING
CONNECTIONS
JUMPER P5
18.4
DEHUMIDIFICATION
For situations where humidity control is a problem, a dehumidifi cation feature has been built into the variable
speed motor. At the start of each cooling cycle, the variable speed motor will run at 82% of the rated airfl ow for
7.5 minutes. After 7.5 minutes has elapsed, the motor will increase to 100% of the rated airfl ow.
There are three jumper wires in front of the thermostat input terminal block that are used in different
applications. These jumper wires may be cut or clipped when the option is not desired.
•
The JW38 jumper not clipped, connects Y1 to Y2 so that the ECM motor only recognizes one input, when
using a single stage thermostat. If you are connecting a single stage A/C unit, input can be on either the
Y or Y2 terminal. If you are connecting a two stage A/C unit, the JW38 jumper must be clipped (1st stage
cool Y1, 2nd stage cool Y2).
•
The JW39 jumper not clipped, connects O to R for using a heat pump in the non-heat pump mode (cooling
only). If the JW39 jumper is clipped, the heat pump will run in heat pump mode.
•
The JW40 jumper not clipped, connects DEHUM to R for dehumidifi cation active all the time. With the
JW40 jumper clipped, the thermostat,or humidstat controls dehumidifi cation.
TABLE 7A - AIR FLOW (Y1-LOW COOL)
WUV060T3AA-N
WUV080T3AA-N
ESP: 0.12" WC - 0.50" WC
A/C Ton
CFM
A/C Ton
3.0T
871
3.0T
2.5T
694
2.5T
2.0T
563
2.0T
1.5T
566
1.5T
TABLE 7B - AIR FLOW (Y2-HIGH COOL)
WUV060T3AA-N
WUV080T3AA-N
ESP: 0.12" WC - 0.50" WC
A/C Ton
CFM
A/C Ton
3.0T
1201
3.0T
2.5T
1013
2.5T
2.0T
823
2.0T
1.5T
630
1.5T
H12.1.14A
5A FUSE
24 VAC MOLEX
ICM
INTERFACE
THERMOSTAT
TERMINALS
FAULT CODE
BUTTON
RED STATUS
LED
WUV080T4BA-N
WUV100T5BA-N
ESP: 0.20" WC - 0.50" WC
CFM
A/C Ton
CFM
A/C Ton
880
4.0T
1109
5.0T
696
3.0T
815
4.0T
2.5T
666
3.0T
570
2.0T
540
2.5T
WUV080T4BA-N
WUV100T5BA-N
ESP: 0.20" WC - 0.50" WC
CFM
A/C Ton
CFM
A/C Ton
1238
4.0T
1680
5.0T
1024
3.0T
1235
4.0T
834
2.5T
1009
3.0T
632
2.0T
818
2.0T
FIGURE 34
WUV120T5BA-N
CFM
A/C Ton
CFM
1309
5.0T
1366
928
4.0T
1070
660
3.0T
791
592
2.5T
666
WUV120T5BA-N
CFM
A/C Ton
CFM
1984
5.0T
2070
1406
4.0T
1621
1000
3.0T
1199
897
2.5T
1009
H22.4A
W415-2306 / C / 09.22.20
49