Exhaust air pipe
1 Air outlet to outdoors
The exhaust air line should be as short and straight as possible.
To avoid excessive noise or a reduced extraction capacity the diameter of the
exhaust air pipeline should not be less than 150 mm.
Use or form only large radius bends. Small radius bends reduce the extraction
capacity of the hood.
Use only smooth pipelines or fl exible hoses of non-fl ammable materials for
the exhaust air pipeline
If the exhaust air pipeline is horizontally routed, there must be a minimum
gradient of 1 cm per metre or an inclination angle of 2°. (Fig. C) Otherwise
condensation water could run into the extractor hood motor.
If the exhaust air is directed into an exhaust air duct, the end of the entry
fitting must be directed in the direction of fl ow.
If the exhaust air pipeline is routed though cool rooms, loft s etc. there can be
a large temperature drop within the individual parts of the pipeline, resulting
in sweating or condensation water production. This renders outlet pipeline
insulation necessary.
In some cases a condensation water barrier must be installed in addition to
adequate insulation.
2 Air outlet via an air shaft