CAUSE OF THE LEAK
OR gasket damaged due to wrong moun-
ting, or defective.
Fitting or outlet plate threads damaged.
The drill-hole on the bar is too big or
misaligned.
Extrusion blowholes into the hollow bar.
Misaligned mounting of the joint in the
corresponding bar seats.
Defects in the seat of O ring of "L" and
"T" joints.
CONdiTiONS FOR THE TRANSPORTATiON OF WATER iN THE HBS SYSTEM
The HBS product by Teseo is suitable to carry water provided that the following conditions are respected.
1. Softened water is to be avoided because of its richness in sodium ions.
2. The acidity must range between pH5 and pH8.
3. The maximum content of chlorine ions must not exceed 2000 mg/L.
4. Iron (Fe), Nickel (Ni), Lead (Pb) and Tin (Sn) must not be present.
5. The maximum Copper (Cu) content should not exceed 0,05 mg/L; the maximum Mercury (Hg) content
should not exceed 0,005 mg/L.
6. Aluminium must not be in direct contact with iron or Copper. Aluminium and Iron must be insulated by
galvanization while aluminium and Copper must be insulated with plastic or inert organic matter.
7. Oxygen, Carbon Dioxide and Ammonia ions, dissolved in water do not cause erosive effects.
8. Water with solution of emulsion oil for the cooling of machinery does not cause any problems.
9. We recommend electrical earth bonding of our pipwork systems in order to avoid any stray currents.
10. We recommend the use of ANODISED bars.
In the eventuality of any doubt, please contact Teseo's Technical Office.
Source: AQM, technical services SINAL Accredited (UNI CEI EN 45001).
REMEDIES
Replace the OR gasket.
Seal with a Teflon band or replace the
faulty piece.
Replace the faulty section of the hollow
bar.
Replace the defective part.
Disassemble the joint and realign the
bars.
Replace faulty joint.